7. Programming
7.2. Read/Write Internal Memory
R200
2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide
103
May 2010
Honeywell
Write Internal Memory
Write instruction is used for writing data from 2MLK CPU module onto High Speed
Counter Module’s internal memory. This is that data which is saved on the CPU's
memory area and the integer [Decimal (00) or Hexadecimal (H00)].
1.
PUT/PUTP Instruction
PUT
Always executed with execution condition On
Level
PUTP
Executed with execution condition of operation Start
Edge
2.
Configuration of PUT/PUTP Instruction
PUT
Execution
condition
n1
n2
n3
n4
Figure 44 – Configuration of PUT/PUTP Instruction
Type
Description
Area Available
n1
Slot No., on which special module is installed
Integer
n2
Start address of special module’s internal memory to write
data.
Integer
n3
Start address of device integer with saved data to write
M, P, K, L, T, C, D, #D
n3
Number of words of data to be written
Integer
a)
Setting base and slot number