R200
2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide
195
May 2010
Honeywell
8. Troubleshooting
8.1 Error Code
This chapter describes the process of diagnosing and solving the errors of High Speed
Counter module.
Errors of High Speed counter module are described below.
Table 27 – Error Code
Error code
(Dec)
Description
RUN LED
status
CH0 CH1
10
Module error (ASIC Reset error)
Blinks every 0.2
sec.
11
Module error (ASIC RAM error)
12
Module error (ASIC Register error)
20
120 Counter type range exceeded
Blinks every 1
sec
21
121 Pulse input type range exceeded
22
122 Auxiliary Mode type range exceeded
23
123 Sampling Count value range exceeded
24
124 Compared output0 type range exceeded
25
125 Compared output1 type range exceeded
26
126 Preset value exceeded counter range
27
127 Ring counter minimum value
≥
Ring counter maximum value
input
28
128 Compared output 0 minimum value exceeded maximum input
range
29
129 Compared output 0 maximum value exceeded maximum input
range
30
130 Compared output 0 minimum value > compared output 0
maximum value set
31
131 Compared output 1 minimum value exceeded maximum input
range
Содержание 2MLF-HD2A
Страница 18: ...Contents Figures xviii 2MLF HO2A 2MLF HD2A High Speed Counter Module User s Guide R200 Honeywell May 2010 ...
Страница 121: ...7 Programming 7 4 Basic Program R200 2MLF HO2A 2MLF HD2A High Speed Counter Module User s Guide 121 May 2010 Honeywell ...
Страница 178: ...7 Programming 7 6 Program 178 2MLF HO2A 2MLF HD2A High Speed Counter Module User s Guide R200 Honeywell May 2010 ...
Страница 222: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...