9. Appendix
9.3. GM Function Block Conversion Program
216
2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide
R200
Honeywell
May 2010
Function Block
type
Classifi
cation
Variable
name
Type
Contents
IN__
MODE
USINT
Pulse
input
type
0
2 phase 1 multiplication
1
2 phase 2 multiplication
2
2 phase 4 multiplication
3
CW/CCW
4
1phase 1input
1multiplication(Program up/down
input)
5
1phase 1input 2multiplication
(Program up/down input)
6
1phase 2input 1multiplication (B
phase up/down input)
7
1phase 2input 2multiplication(B
phase up/down input)
RING_MIN
DINT
Ring upper
limit
-2,147,483,648 ~ 2,147,483,647
RING_MAX
DINT
Ring lower limit
-2,147,483,648 ~ 2,147,483,647
Output
DONE
BOOL
Execution status
If it completes, it outputs 1 and
holds. If error occurs, it outputs 0
STAT
USINT
Error status
In case of error, outputs error code
2.
Mode setting function block of 2MLI/2MLR
Since 2MLI/2MLR cannot process Mode setting Function Block (HSCC_MOD)
at once like GM, it combines methods such as count type, pulse input type, Ring
upper/lower count to execute function block.
Содержание 2MLF-HD2A
Страница 18: ...Contents Figures xviii 2MLF HO2A 2MLF HD2A High Speed Counter Module User s Guide R200 Honeywell May 2010 ...
Страница 121: ...7 Programming 7 4 Basic Program R200 2MLF HO2A 2MLF HD2A High Speed Counter Module User s Guide 121 May 2010 Honeywell ...
Страница 178: ...7 Programming 7 6 Program 178 2MLF HO2A 2MLF HD2A High Speed Counter Module User s Guide R200 Honeywell May 2010 ...
Страница 222: ...Honeywell Process Solutions 1860 W Rose Garden Lane Phoenix AZ 85027 USA ...