GENERATOR/CHARGING SYSTEM
8-4
From page 8-3
Light is ON
Abnormal
Abnormal
Abnormal
Light OFF
Light is ON
Normal
Normal
Normal
Check whether the overload indicator light (red) is
ON.
Disconnect the AC receptacle. Verify that the
cooling air duct is not blocked and the generator
is not placed near a wall.
Correct the above problems, and restart the
engine.
Check the AC circuit protector (page 8-28).
*Equipped type only
Replace the inverter unit (page 8-7).
Replace the AC circuit protector (page 8-13).
Replace the AC receptacle (page 8-13).
Remove the inverter unit (page 8-7).
Measure the resistance between the terminals of
the main coil 4P connector.
Resistance:
No.2 (R) - No.3 (W): 0.6 - 1.1
Ω
No.3 (W) - No.4 (Bu): 0.6 - 1.1
Ω
No.2 (R) - No.4 (Bu): 0.6 - 1.1
Ω
Check the harness connecting the inverter unit
and generator for an open or short circuit and for
proper connection.
Replace the inverter unit (page 8-7).
Check the AC receptacle.
7
2
3
4
10
Viewed from terminal side
GENERATOR WIRE HARNESS
R
W
B u
2
3
4
10
Viewed from terminal side
Replace or repair the generator wire
harness (page 8-10).
Replace the stator (page 8-10).
Normal
Abnormal
Содержание EU3000i Handi
Страница 37: ...MEMO ...
Страница 73: ...MEMO ...
Страница 75: ...FUEL SYSTEM 6 2 FUEL SYSTEM TOOLS Float level gauge 07401 0010000 ...
Страница 97: ...MEMO ...
Страница 105: ...GENERATOR CHARGING SYSTEM 8 2 GENERATOR CHARGING SYSTEM TOOLS Flywheel puller set 07935 8050004 ...
Страница 133: ...MEMO ...
Страница 149: ...MEMO ...
Страница 150: ...12 1 12 12 MUFFLER MUFFLER REMOVAL INSTALLATION 12 2 ...
Страница 179: ...MEMO ...
Страница 180: ...16 1 16 16 TECHNICAL FEATURES FRAME MADE OF MAGNESIUM 16 2 INDICATOR 16 3 ...
Страница 185: ...MEMO ...
Страница 186: ...17 1 17 17 WIRING DIAGRAMS HOW TO READ A WIRING DIAGRAM RELATED INFORMATION 17 2 WIRING DIAGRAMS 17 4 ...
Страница 193: ...MEMO ...