13) Manual Start

Set the Auto-Manual-Test selector to the Manual position. Nothing will happen until you press the 
Manual Start pushbutton. Then, the fuel solenoid will on and EST off. The Start relay will respond 
each time you press the button. Bypass on the CCR and GRR relay and the Manual Start pushbutton 
is  disabled.  The OPT  will  on and up the OPR and the generator is  in operation.  To stop the 
generator you either turn the selector to Auto for automatic shutdown or press the Emergency Stop 
pushbutton.

14) Test Start

Set the Auto-Manual-Test selector to the Test position. Immediately the ASR will begin the Crank 
and Rest cycle. The fuel solenoid will on and the EST will off. Bypass on the CCR  and GRR. The 
OPT will on and up the OPR and the generator is in operation. To stop the generator you either turn 
the selector to Auto for automatic shutdown or press the Emergency Stop pushbutton.

15) Optional Outputs

There are a few outputs not mentioned in the testing procedure above. They are the FMR output, 
Flashing output, Oil Pressure Timer output and Fused +ve out. If you are using any of those optional 
outputs, test that they are in working order.
You can add a relay to the FMR output and use the contacts for remote signaling to the BAS 
(Building Automation System) or the guard house to warn that the gen-set has failed. Take note that 
the FMR does not give an output for FAR cards that is set for no shut down.
By adding a relay to the flashing output, you can series the NO contacts with the bell thus causing it 
to ring on and off.
Four nos. OPR contacts are provided, but if they are insufficient, you can add a relay to the Oil 
Pressure Timer output for additional contacts.
You can use the Fused +ve out terminal (T02) as a power source for additional controls if needed. It 
is protected by the 10A fuse on the base PCB.

TROUBLE SHOOTING

The HAMF-8 / 4 is designed in such a way that parts replacement are easy and of minimal costs in 
comparison to the cost of the whole unit. There are 21 / 16 plug-in relay cards of only 13 different types. 
ESR and FMR are the same while there are 8 / 4 nos. of FAR. The only electronic components on the 
base PCB are 3 nos. 6A 1000V rectifier diodes. Their function is to blow the fuse in case of reverse 
polarity connection of the input supply. They also help to absorb feedback from inductive load which may 
be harmful to some of the relay cards. Lastly, they block the energy stored in the 10,000uF 50V capacitor, 
from flowing out when there is a sudden drop in voltage while the Start Relay is being cranked.

Before we continue further, there is one thing you should take note. The most expensive and difficult to 
replace part of the HAMF-8/4 is the base PCB. Therefore, care should be taken, to ensure it does not get 
damaged. Here are few pointers:

1) Only replace with correct amperage fuse i.e. 10Amps. Two spare fuses are provided. Even though the 
base PCB track width is 3 times (3mm) the relay cards track width (1mm), the high energy of a battery 
can damage it, if not protected by a fuse.

2) Do not allow small metal parts like screws, washers etc. to fall in between the base PCB and metal 
panel. The reason is obvious.

Page 14

HOKKIM

giving you control

Control & Protection Relays

Содержание HAMF-4

Страница 1: ... show the bottom base Printed Circuit Board with labeling of terminals and plug in PCB cards We will now identify each PCB card and familiarize you with the LED indicating lights and knob adjustments Once familiarized you will be able to follow the operation of the Integrated AMF and identify problems when they occur and replace the appropriate card 1 ESR Emergency Stop Relay RUN green LED On Rela...

Страница 2: ...Page 2 HOKKIM giving you control Control Protection Relays ...

Страница 3: ...Page 3 HOKKIM giving you control Control Protection Relays ...

Страница 4: ...Page 4 HOKKIM giving you control Control Protection Relays ...

Страница 5: ...Page 5 HOKKIM giving you control Control Protection Relays ...

Страница 6: ... off the lamp output relay in the Fault Alarm Relay card Adjustment Flashing rate from slow to fast and steady 12 FAR Fault Alarm Relay LAMP amber LED On Lamp relay energized and output to external lamp ALARM red LED On Fault signal detected and alarm activated Selection Loop to next FAR or Out to FMR 13 OPR Oil Pressure Relay Provides 4 nos delay on contacts set by OPT for fault alarm signals 14 ...

Страница 7: ...Page 7 HOKKIM giving you control Control Protection Relays ...

Страница 8: ...ectable Normally Open or Normally Close T12 To Mains Fail contact selectable Normally Open or Normally Close T13 To Bell Cancel push button Normally Open T14 To Bell Cancel push button Normally Open T15 To Alarm Reset push button Normally Close T16 To Alarm Reset push button Normally Close T17 Negative supply input from battery T18 Negative supply output Internally connected to T17 T19 Positive su...

Страница 9: ...To indicator lamp No 2 corresponding to S2 L3 To indicator lamp No 3 corresponding to S3 L4 To indicator lamp No 4 corresponding to S4 L5 To indicator lamp No 5 corresponding to S5 L6 To indicator lamp No 6 corresponding to S6 L7 To indicator lamp No 7 corresponding to S7 L8 To indicator lamp No 8 corresponding to S8 TERMINALS S1 TO S8 FAULT SIGNAL INPUTS S1 To volt free fault signal contacts Norm...

Страница 10: ...You can have options of 1 2 or 4 oil pressure delay contacts TERMINALS C1 TO C8 ALARM EXTENSION C1 To Extension Fault Alarm Relay Board FARX terminal R1 For use if required C2 To Extension Fault Alarm Relay Board FARX terminal R2 For use if required C3 To Extension Fault Alarm Relay Board FARX terminal R3 For use if required C4 To Extension Fault Alarm Relay Board FARX terminal R4 For use if requi...

Страница 11: ...Examples are Low Fuel or Charger Fail The FAR allows you to set these parameters There is a switch at the bottom corner labeled Loop and Out see diagram The FARs should all be set to Loop until the last one which should be set to Out to the Fault Monitor Relay Example 1 All faults require shut down of generator Set FAR No 1 to No 7 to Loop and No 8 to Out All the red LEDs in the FAR card are on Ex...

Страница 12: ...ing from No 1 to 8 It should be noted that fault signal which is loop through the OPR contacts cannot be triggered externally When one or more fault is triggered the following should happen The FMR will trip this is only true if the fault Loop Out has not been disabled The Bell LED will light and external bell ring The corresponding Lamp LED will flash together with the external lamp The correspon...

Страница 13: ...afety and sometimes is not used 10 OPR Fault Simulation Repeat steps 3 5 6 with fault inputs loop through the OPR 11 14 21 24 31 34 41 44 contacts Fault can only be stimulated after the OPT is up and OPR energized It can be noted that each time a fault is stimulated the FMR trips cutting supply to MFT SDT GRR CCR OPT OPR The EST will on and after the set delay up and releases the external stop sol...

Страница 14: ...l thus causing it to ring on and off Four nos OPR contacts are provided but if they are insufficient you can add a relay to the Oil Pressure Timer output for additional contacts You can use the Fused ve out terminal T02 as a power source for additional controls if needed It is protected by the 10A fuse on the base PCB TROUBLE SHOOTING The HAMF 8 4 is designed in such a way that parts replacement a...

Страница 15: ...ng strike the Under Voltage Relay and cause a flash over to its relay contacts After taking care that the base PCB is not damaged trouble shooting the HAMF 8 4 is easy in the worse scenario all you have to do is to replace all the 21 16 relay cards which takes less then 10 minutes To replace any relay card you have to remove the six knobs and six mounting screws of the top face label plate After r...

Отзывы: