PREPARATIONS BEFORE WIRING

There are certain parameters to be set in the HAMF-8/4. It is easier to do so 
before wiring up the unit because of accessibility. They are as follows:-

1)

Mains Fail Timer   In addition to the time delay adjustment at 

the top, the MFT allows you to choose between Normally Open or 
Normally Close contacts to start the generator. Look at the left hand 
side of the MFT and you will see a switch. It is labeled NO and NC (see diagram). Select as required.

2)

Attempt Start Relay   The ASR allows you to select the number of 

attempts the relay makes before sending a fail to start signal to the fault 
alarm relay. Look at the right hand side of the relay. You will see the 10-
way DIP switch (see diagram). To select the number of attempt required, 
push one of the switch to the ON position. Note: switch No.10 gives the 
same number of attempts as No. 9. If non of the switch is selected, the relay 
will attempt start continuously. Do 

NOT

 push on more than one switch

3)

Lamp Flashing Relay  The LFR is factory set at a rate of 90 cycle per minute. If 

another rate of flashing is preferred, it can be adjusted to a faster rate by turning the 
Preset anti-clockwise and vice versa. The Preset is located on the left hand side of the 
relay (see diagram). To adjust it you need a slim and long insulated screw driver.

4)

Fault Alarm Relay   There are certain fault signals that do not 

require   shut-down   of   the   generator.   Examples   are:   Low   Fuel   or 
Charger Fail. The FAR allows you to set these parameters. There is a 
switch at the bottom corner labeled Loop and Out (see diagram). The FARs should all be set to Loop 
until the last one which should be set to Out to the Fault Monitor Relay.

Example 1:

All faults require shut-down of generator. Set FAR No.1 to No.7 to Loop and No.8 to 
Out.  All the red LEDs in the FAR card are on. 

Example 2:

Two faults does not require shut-down of generator. Set FAR No. 1 to No. 5 to Loop 
and No. 6 to Out. The setting of No.7 and No. 8 do not matter as they are disabled 
and will not effect shut-down. Notice that the red LEDs in the FAR cards No.7 and 
No.8 are off. The same rule follows if an 

FARX

 extension is added. Any FAR that 

comes after the one that is set to Out is disabled. At least one FAR has to be set to 
Out or the FMR will not energize (Trip).

INSTALLATION AND WIRING

The HAMF-8/4 has a metal base plate with mounting holes in each corner. Place the unit onto your 
switchboard panel and mark the holes. Drill and tap accordingly. After cleaning, mount the unit with 
appropriate screws and washers. Commence wiring by referring to Fig. 5. If possible, label the wires 
according to the terminal markings. This allows for easier trouble shooting. Some of the terminations will 
not be required as the unit allows for various possibilities. Do Not over tighten the terminal screws, if you 
damage the terminal, the unit has to be send back to our factory for parts replacement. The base PCB does 
not have user replaceable parts except the 10A glass fuse.

Page 11

HOKKIM

giving you control

Control & Protection Relays

Содержание HAMF-4

Страница 1: ... show the bottom base Printed Circuit Board with labeling of terminals and plug in PCB cards We will now identify each PCB card and familiarize you with the LED indicating lights and knob adjustments Once familiarized you will be able to follow the operation of the Integrated AMF and identify problems when they occur and replace the appropriate card 1 ESR Emergency Stop Relay RUN green LED On Rela...

Страница 2: ...Page 2 HOKKIM giving you control Control Protection Relays ...

Страница 3: ...Page 3 HOKKIM giving you control Control Protection Relays ...

Страница 4: ...Page 4 HOKKIM giving you control Control Protection Relays ...

Страница 5: ...Page 5 HOKKIM giving you control Control Protection Relays ...

Страница 6: ... off the lamp output relay in the Fault Alarm Relay card Adjustment Flashing rate from slow to fast and steady 12 FAR Fault Alarm Relay LAMP amber LED On Lamp relay energized and output to external lamp ALARM red LED On Fault signal detected and alarm activated Selection Loop to next FAR or Out to FMR 13 OPR Oil Pressure Relay Provides 4 nos delay on contacts set by OPT for fault alarm signals 14 ...

Страница 7: ...Page 7 HOKKIM giving you control Control Protection Relays ...

Страница 8: ...ectable Normally Open or Normally Close T12 To Mains Fail contact selectable Normally Open or Normally Close T13 To Bell Cancel push button Normally Open T14 To Bell Cancel push button Normally Open T15 To Alarm Reset push button Normally Close T16 To Alarm Reset push button Normally Close T17 Negative supply input from battery T18 Negative supply output Internally connected to T17 T19 Positive su...

Страница 9: ...To indicator lamp No 2 corresponding to S2 L3 To indicator lamp No 3 corresponding to S3 L4 To indicator lamp No 4 corresponding to S4 L5 To indicator lamp No 5 corresponding to S5 L6 To indicator lamp No 6 corresponding to S6 L7 To indicator lamp No 7 corresponding to S7 L8 To indicator lamp No 8 corresponding to S8 TERMINALS S1 TO S8 FAULT SIGNAL INPUTS S1 To volt free fault signal contacts Norm...

Страница 10: ...You can have options of 1 2 or 4 oil pressure delay contacts TERMINALS C1 TO C8 ALARM EXTENSION C1 To Extension Fault Alarm Relay Board FARX terminal R1 For use if required C2 To Extension Fault Alarm Relay Board FARX terminal R2 For use if required C3 To Extension Fault Alarm Relay Board FARX terminal R3 For use if required C4 To Extension Fault Alarm Relay Board FARX terminal R4 For use if requi...

Страница 11: ...Examples are Low Fuel or Charger Fail The FAR allows you to set these parameters There is a switch at the bottom corner labeled Loop and Out see diagram The FARs should all be set to Loop until the last one which should be set to Out to the Fault Monitor Relay Example 1 All faults require shut down of generator Set FAR No 1 to No 7 to Loop and No 8 to Out All the red LEDs in the FAR card are on Ex...

Страница 12: ...ing from No 1 to 8 It should be noted that fault signal which is loop through the OPR contacts cannot be triggered externally When one or more fault is triggered the following should happen The FMR will trip this is only true if the fault Loop Out has not been disabled The Bell LED will light and external bell ring The corresponding Lamp LED will flash together with the external lamp The correspon...

Страница 13: ...afety and sometimes is not used 10 OPR Fault Simulation Repeat steps 3 5 6 with fault inputs loop through the OPR 11 14 21 24 31 34 41 44 contacts Fault can only be stimulated after the OPT is up and OPR energized It can be noted that each time a fault is stimulated the FMR trips cutting supply to MFT SDT GRR CCR OPT OPR The EST will on and after the set delay up and releases the external stop sol...

Страница 14: ...l thus causing it to ring on and off Four nos OPR contacts are provided but if they are insufficient you can add a relay to the Oil Pressure Timer output for additional contacts You can use the Fused ve out terminal T02 as a power source for additional controls if needed It is protected by the 10A fuse on the base PCB TROUBLE SHOOTING The HAMF 8 4 is designed in such a way that parts replacement a...

Страница 15: ...ng strike the Under Voltage Relay and cause a flash over to its relay contacts After taking care that the base PCB is not damaged trouble shooting the HAMF 8 4 is easy in the worse scenario all you have to do is to replace all the 21 16 relay cards which takes less then 10 minutes To replace any relay card you have to remove the six knobs and six mounting screws of the top face label plate After r...

Отзывы: