TESTING

After completing the wiring, use a continuity tester to check that the wiring are properly done and the unit 
is ready for testing. It should be noted that the HAMF-8 / 4 is only designed for 12VDC or 24VDC. Do 
Not feed 240VAC mains supply into any part of the unit as it will definitely be damaged. Make sure the 
+ve output to relays, push buttons, selector switch, bell or lamps is not shorted to ground or the 10A fuse 
will blow. As the testing process is long, it is broken into steps, at any time feel free to repeat the steps, as 
follows:
1)

Check Voltage
Check the charger and battery voltage. It should be around 27VDC or 13.5VDC depending on the 
battery type used.

2)

Switch On
Switch On the circuit breaker. Notice that the ESR Run, FMR Run and EST On LED are lighted. At 
the same time the Energize Stop Relay should be engaged. After the set delay, the EST Up LED is 
lighted and the Energize Stop Relay is released. Check the voltage across terminal T01 & T17 it 
should be same as the battery. Then check the voltage across terminal T17 & S1 - S8 it should be 
one half (1/2) the battery voltage.

3)

Fault Stimulation
Using a short wire with both ends strip of insulation, short the fault signal input to ve or -ve 
as desired starting from No. 1 to 8. It should be 
noted that fault signal which is loop through the 
OPR contacts cannot be triggered externally. When 
one or more fault is triggered, the following should 
happen: The FMR will trip (this is only true if the 
fault   Loop/Out   has   not   been   disabled).   The   Bell   LED   will   light   and   external   bell   ring.   The 
corresponding Lamp LED will flash together with the external lamp. The corresponding Alarm LED 
will light.
Note: It has come to our attention that certain  Caterpillar  or  Cummins  engines which give a +ve 
fault signal are sensitive to the one half (1/2) supply voltage at the fault input S1 - S8. A reverse 
blocking diode (1N5408) is required to prevent false triggering. See diagram for connection

4)

Flashing Rate
The rate of lamp flashing can be adjusted. Turn the Preset on the LFR

 

card clockwise and the rate is 

slower. Anti-clockwise and the rate is faster. Fully anti-clockwise and the lamp is steady On. Use a 
slim and long insulated screw driver.

5)

Bell Cancel
Press the Alarm Cancel button and notice that the Cancel LED will light. At the same time the 
external bell is silenced and the Bell LED no longer lighted. All corresponding Lamp LEDs and 
external lamps remained steady On.

6)

Alarm Reset
Press the Reset button and notice the Lamp and Alarm LED goes off. In case the external fault is 
still present the fault alarm is re-triggered as in step 3.

Page 12

HOKKIM

giving you control

Control & Protection Relays

Содержание HAMF-4

Страница 1: ... show the bottom base Printed Circuit Board with labeling of terminals and plug in PCB cards We will now identify each PCB card and familiarize you with the LED indicating lights and knob adjustments Once familiarized you will be able to follow the operation of the Integrated AMF and identify problems when they occur and replace the appropriate card 1 ESR Emergency Stop Relay RUN green LED On Rela...

Страница 2: ...Page 2 HOKKIM giving you control Control Protection Relays ...

Страница 3: ...Page 3 HOKKIM giving you control Control Protection Relays ...

Страница 4: ...Page 4 HOKKIM giving you control Control Protection Relays ...

Страница 5: ...Page 5 HOKKIM giving you control Control Protection Relays ...

Страница 6: ... off the lamp output relay in the Fault Alarm Relay card Adjustment Flashing rate from slow to fast and steady 12 FAR Fault Alarm Relay LAMP amber LED On Lamp relay energized and output to external lamp ALARM red LED On Fault signal detected and alarm activated Selection Loop to next FAR or Out to FMR 13 OPR Oil Pressure Relay Provides 4 nos delay on contacts set by OPT for fault alarm signals 14 ...

Страница 7: ...Page 7 HOKKIM giving you control Control Protection Relays ...

Страница 8: ...ectable Normally Open or Normally Close T12 To Mains Fail contact selectable Normally Open or Normally Close T13 To Bell Cancel push button Normally Open T14 To Bell Cancel push button Normally Open T15 To Alarm Reset push button Normally Close T16 To Alarm Reset push button Normally Close T17 Negative supply input from battery T18 Negative supply output Internally connected to T17 T19 Positive su...

Страница 9: ...To indicator lamp No 2 corresponding to S2 L3 To indicator lamp No 3 corresponding to S3 L4 To indicator lamp No 4 corresponding to S4 L5 To indicator lamp No 5 corresponding to S5 L6 To indicator lamp No 6 corresponding to S6 L7 To indicator lamp No 7 corresponding to S7 L8 To indicator lamp No 8 corresponding to S8 TERMINALS S1 TO S8 FAULT SIGNAL INPUTS S1 To volt free fault signal contacts Norm...

Страница 10: ...You can have options of 1 2 or 4 oil pressure delay contacts TERMINALS C1 TO C8 ALARM EXTENSION C1 To Extension Fault Alarm Relay Board FARX terminal R1 For use if required C2 To Extension Fault Alarm Relay Board FARX terminal R2 For use if required C3 To Extension Fault Alarm Relay Board FARX terminal R3 For use if required C4 To Extension Fault Alarm Relay Board FARX terminal R4 For use if requi...

Страница 11: ...Examples are Low Fuel or Charger Fail The FAR allows you to set these parameters There is a switch at the bottom corner labeled Loop and Out see diagram The FARs should all be set to Loop until the last one which should be set to Out to the Fault Monitor Relay Example 1 All faults require shut down of generator Set FAR No 1 to No 7 to Loop and No 8 to Out All the red LEDs in the FAR card are on Ex...

Страница 12: ...ing from No 1 to 8 It should be noted that fault signal which is loop through the OPR contacts cannot be triggered externally When one or more fault is triggered the following should happen The FMR will trip this is only true if the fault Loop Out has not been disabled The Bell LED will light and external bell ring The corresponding Lamp LED will flash together with the external lamp The correspon...

Страница 13: ...afety and sometimes is not used 10 OPR Fault Simulation Repeat steps 3 5 6 with fault inputs loop through the OPR 11 14 21 24 31 34 41 44 contacts Fault can only be stimulated after the OPT is up and OPR energized It can be noted that each time a fault is stimulated the FMR trips cutting supply to MFT SDT GRR CCR OPT OPR The EST will on and after the set delay up and releases the external stop sol...

Страница 14: ...l thus causing it to ring on and off Four nos OPR contacts are provided but if they are insufficient you can add a relay to the Oil Pressure Timer output for additional contacts You can use the Fused ve out terminal T02 as a power source for additional controls if needed It is protected by the 10A fuse on the base PCB TROUBLE SHOOTING The HAMF 8 4 is designed in such a way that parts replacement a...

Страница 15: ...ng strike the Under Voltage Relay and cause a flash over to its relay contacts After taking care that the base PCB is not damaged trouble shooting the HAMF 8 4 is easy in the worse scenario all you have to do is to replace all the 21 16 relay cards which takes less then 10 minutes To replace any relay card you have to remove the six knobs and six mounting screws of the top face label plate After r...

Отзывы: