8.7.4 Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind function
prevails.
Anti-cold wind control function at heating mode (T=indoor exchanger temp.)
T
T temp. up
T temp. down
Setting fan speed
Breeze
Fan off
TE3
TE1
TE4
TE2
8.7.5 Auto wind at heating mode (T=indoor temp.)
0
T-Ts
Room temp. up
Room temp. down
2
Low fan
Med fan
8.7.6 Indoor evaporator high-temperature protection at heating mode
(T=indoor exchanger temp.)
21