Connections
22
Doc.ID. HMSI-168-92
Netbiter EasyConnect
Doc.Rev. 2.10
When the SIM card is in place, and the required inputs/outputs have been connected, Netbiter Easy-
Connect EC250 can be powered up. The rest of the configuration is done via Netbiter Argos. See
page 40 for further information.
To extract the SIM card, simply press again to release.
4.3.5 Antenna Connector
The antenna connector is a standard female SMA screw connector. Optional external antennas are avail-
able from your supplier.
4.4 Netbiter EasyConnect EC350
4.4.1 Terminal Block (11-pin)
Digital Inputs (DI)
Netbiter EasyConnect EC350 features 2 digital inputs of the dry contact type, i.e. they do not require
any control voltage, and will function with a switch or breaker. Please observe the following for the dig-
ital inputs:
• Max recommended cable length = 3m. It may be possible to use the inputs with longer cable
lengths, but this may give rise to problems.
•
Do not apply a power source to the digital input, as there is a risk it will burn out.
Relay Output (Digital Output)
There is one relay output with a rated load of 1A at 24V DC.
The relay output must be supplied from an isolating transformer using a secondary listed fuse rated at
maximum 3.3A and minimum 30V DC.
No.
Label
Function
11
(Analog In) COM
Analog ground
10
(Analog In) AI4
Analog Input #4
9
(Analog In) AI3
Analog Input #3
8
(Analog In) AI2
Analog Input #2
7
(Analog In) AI1
Analog input #1
6
(DI/pulse In) DI2-
Digital input 2
5
(DI/pulse In) DI2+
Digital input 2 current source
4
(DI/pulse In) DI1-
Digital input 1
3
(DI/pulse In) DI1+
Digital input 1 current source
2
(Relay) COM
Relay Output, COM, Isolated
1
(Relay) NO
Relay output, NO, isolated