Aquarea H Generation includes the possibility to control up to 2 different zones. The register 82
(Modbus protocol address) indicates the number of zones configured in the Hydro unit: 1 or 2
zones.
Taking this information into account and only in case that Hydro unit is controlling 2 zones, the
register address 9 (Modbus protocol address) can be used to switch on/off the zones. Notice
that if the Hydro unit is configured to manage a single zone, the use of the register address 9
(Modbus protocol address)
doesn’t
have any effect.
Please, check the Hydro Unit User
’s M
anual for more information about the zone
s’
configuration
and their options.
4.3
DIP-switch Configuration Interface
All the configuration values on INMBSPAN001A000 can be written and read from Modbus
interface. Otherwise, some of them can also be setup from its on-board DIP-switch interface.
The device has DIP-switches SW1, SW3
and SW4 on the following locations:
The following tables apply to the interface´s configuration through DIP-switches:
SW1
–
Hydro
unit’s features
SW1-P1..4 Description
Set point limits are defined by the configuration of Aquarea H Generation Unit (Default value).
Set point limits are the maximum ones allowed by the manufacturer, not considering the specific
Aquarea H Generation Unit
’s limits
Reserved, not used (Default value)
Reserved, not used
SW3
SW4
FIXING
CABLE
EIA485
A B
Hydro Unit
SW1
SW1
SW4
ON
1 2 3 4
ON
SW3
1 2 3 4
1 2 3 4 5 6 7 8
ON
ON
ON
ON
ON