7.

 

Error Codes 

 

Error 

Code 

Modbus

 

Error in 
Remote 

Controller 

Error Description 

H00 

No abnormality detected 

112 

H12 

Indoor/Outdoor capacity unmatched 

115 

H15 

Outdoor compressor temperature sensor abnormality 

120 

H20 

Water pump abnormality 

123 

H23 

Indoor refrigerant liquid temperature sensor abnormality 

127 

H27 

Service valve error 

128 

H28 

Abnormal solar sensor 

131 

H31 

Abnormal swimming pool sensor 

136 

H36 

Abnormal buffer tank sensor 

138 

H38 

Brand code not match 

142 

H42 

Compressor low pressure abnormality 

143 

H43 

Abnormal Zone 1 sensor 

144 

H44 

Abnormal Zone 2 sensor 

162 

H62 

Water flow switch abnormality 

163 

H63 

Refrigerant low pressure abnormality 

164 

H64 

Refrigerant high pressure abnormality 

165 

H65 

Deice circulation error 

167 

H67 

Abnormal External Thermistor 1 

168 

H68 

Abnormal External Thermistor 2 

170 

H70 

Back-up heater OLP abnormality 

172 

H72 

Tank sensor abnormal 

174 

H74 

PCB communication error 

175 

H75 

Low water temperature control 

176 

H76 

Indoor - control panel communication abnormality 

190 

H90 

Indoor/outdoor abnormal communication 

191 

H91 

Tank heater OLP abnormality 

195 

H95 

Indoor/Outdoor wrong connection 

198 

H98 

Outdoor high pressure overload protection 

199 

H99 

Indoor heat exchanger freeze prevention 

212 

F12 

Pressure switch activate 

214 

F14 

Outdoor compressor abnormal revolution 

215 

F15 

Outdoor fan motor lock abnormality 

216 

F16 

Total running current protection 

220 

F20 

Outdoor compressor overheating protection 

222 

F22 

IPM (power transistor) overheating protection 

223 

F23 

Outdoor Direct Current (DC) peak detection 

224 

F24 

Refrigeration cycle abnormality 

225 

F25 

Cooling/Heating cycle changeover abnormality 

227 

F27 

Pressure switch abnormality 

229 

F29 

Low Discharge Superheat 

230 

F30 

Water outlet sensor 2 abnormality 

232 

F32 

Abnormal Internal Thermostat 

236 

F36 

Outdoor air temperature sensor abnormality 

237 

F37 

Indoor water inlet temperature sensor abnormality 

240 

F40 

Outdoor discharge pipe temperature sensor abnormality 

241 

F41 

PFC control 

242 

F42 

Outdoor heat exchanger temperature sensor abnormality 

243 

F43 

Outdoor defrost sensor abnormality 

245 

F45 

Indoor water outlet temperature sensor abnormality 

246 

F46 

Outdoor Current Transformer open circuit 

248 

F48 

Outdoor EVA outlet temperature sensor abnormality 

Содержание INTESIS INMBSPAN001A000

Страница 1: ...Modbus RTU EIA 485 Interface for Panasonic Air to Water systems Compatible with Panasonic Aquarea H generation models USER MANUAL Issue date 05 2020 r1 3 ENGLISH...

Страница 2: ...ll rights reserved This information is subject to change without notice URL https www intesis com 2 22 Modbus RTU EIA 485 Interface for Panasonic Air to Water systems Compatible with Panasonic Aquarea...

Страница 3: ...nd are only intended to help improve understanding of the functionality and handling of the product In view of the wide range of possible applications of the product and because of the many variables...

Страница 4: ...fication 8 4 1 Modbus physical layer 8 4 2 Modbus Registers 8 4 2 1 General System Control 8 4 2 2 Zones 9 4 2 3 Tank Configuration 10 4 2 4 Consumption 11 4 2 5 Maintenance 11 4 2 6 Unit Configuratio...

Страница 5: ...Direct connection to Modbus RTU EIA 485 networks Up to 63 INMBSPAN001A000 devices can be connected in the same network INMBSPAN001A000 is a Modbus slave device Direct connection to the Hydro unit Up...

Страница 6: ...ered part to the socket CN CNT of the Hydro unit s electronic circuit You can place the INMBSPAN001A000 inside or outside the Hydro unit depending on your needs Remember that the INMBSPAN001A000 must...

Страница 7: ...ing the instructions of the diagram above 4 Connect the EIA 485 bus to the connector EIA485 of the interface 5 Close the Hydro indoor unit 6 Check the DIP Switch configuration of the Intesis interface...

Страница 8: ...and they use the standard Modbus big endian notation 4 2 1 General System Control Register Address protocol address Register Address PLC address R W Description 0 1 R W System On Off 0 Off 1 On Defau...

Страница 9: ...3 Internal room sensor 4 Room thermistor 5 Pool Sensor 12 13 R W Zone 1 setpoint temperature 3 4 COOL Water shift 5 5 C C x10 C 41 41 F Water 5 20 C C x10 C 41 68 F Room 18 35 C C x10 C 64 4 95 F HEAT...

Страница 10: ...emperature setting mode 3 4 1 Room temperature 2 Compensation curve Water Temp 3 Direct Water Temp 4 Pool Temp 18 19 R Zone 1 min Setpoint temperature 1 3 Any C x10 C 19 20 R Zone 1 max Setpoint tempe...

Страница 11: ...intenance Register Address protocol address Register Address PLC address R W Description 52 53 R Error Code 5 0 No Error 0xxx U err 1xxx H err 2xxx F err 64 65 R Device Status 1 Off 2 On 70 71 R Curre...

Страница 12: ...re s values temperature registers are expressed according to the temperature s format configured through its onboard DIP Switches See 4 3 DIP switch Configuration Interface These following formats are...

Страница 13: ...lease check the Hydro Unit User s Manual for more information about the zones configuration and their options 4 3 DIP switch Configuration Interface All the configuration values on INMBSPAN001A000 can...

Страница 14: ...d not used Reserved not used Default value Reserved not used Table 4 1 SW1 Hydro unit s features SW3 SW4 Baud rate configuration SW3 P7 8 SW4 P3 Description 2400bps 4800bps 9600bps Default value 19200...

Страница 15: ...cription Temperature values in Modbus register are represented in degrees x1 Default value Temperature values in Modbus register are represented in decidegrees x10 Temperature values in Modbus registe...

Страница 16: ...s Add SW3 P1 6 Add SW3 P1 6 Add SW3 P1 6 Add SW3 P1 6 Add SW3 P1 6 0 13 26 39 52 1 14 27 40 53 2 15 28 41 54 3 16 29 42 55 4 17 30 43 56 5 18 31 44 57 6 19 32 45 58 7 20 33 46 59 8 21 34 47 60 9 22 35...

Страница 17: ...s be 1 when this function is being used in case of writing 4 5 Device LED indicator The device includes two LED indicators to show all the possible operational states In the following table there are...

Страница 18: ...transmitters outputs are in three state high impedance it is also required a fail safe biasing mechanism This mechanism provides a safe status a correct voltage level in the bus when all the transmit...

Страница 19: ...s For terminal solid wires or stranded wires twisted or with ferrule 1 core 0 5mm2 2 5mm2 2 cores 0 5mm2 1 5mm2 3 cores not permitted Stock Humidity 95 RH non condensing Modbus RTU port 1 x Serial EIA...

Страница 20: ...tion is subject to change without notice URL https www intesis com 20 22 6 List of supported Hydro Unit Types A list of Panasonic Hydro unit model s references compatible with INMBSPAN001A000 and thei...

Страница 21: ...emperature control 176 H76 Indoor control panel communication abnormality 190 H90 Indoor outdoor abnormal communication 191 H91 Tank heater OLP abnormality 195 H95 Indoor Outdoor wrong connection 198...

Страница 22: ...change without notice URL https www intesis com 22 22 Error Code Modbus Error in Remote Controller Error Description 249 F49 Outdoor bypass outlet temperature sensor abnormality 295 F95 Cooling high...

Отзывы: