Intesis

TM

 INMBSPAN001A000

 

User’s Manual r1.

3 EN

 

 

 

 

  

 

 

 

 

 

 

© HMS Industrial Networks S.L.U. - All rights reserved 

This information is subject to change without notice

 

 

  URL    https://www.intesis.com  

 
 

                12 / 22

 

4.2.7

 

Device registers 

 

Register Address 

(protocol address) 

Register Address  

(PLC address) 

R/W  Description 

49 

50 

Device ID: 0x0D00

 

50 

51 

Software version

 

 

4.2.8

 

Considerations on Temperature Registers 

 
Setpoint temperature may be controlled from 4 different internal parameters of the Hydro Unit: 

Water shift

Water

Room

 and 

Pool

.  

 
All these parameters depend on the configuration of the 

Zone setup

Zone temp. setting

 

mode

 

and 

Operation Mode

 
Find  below  the  correspondence  of  this  configuration  to  know  which  internal  parameter  is 
modified when we are controlling registers 12 and 13 (Modbus Protocol Address), corresponding 
to 

Zone 1 setpoint temperature

 and 

Zone 2 setpoint temperature

 respectively.  

 

 
Notice  that  temperature

’s

  values  temperature  registers  are  expressed  according  to  the 

temperature´s  format  configured  through  its  onboard  DIP-Switches  (See 

4.3  -  DIP-switch 

Configuration Interface

”)

. These following formats are possible: 

 

 

Celsius value

: Value in Modbus register is the temperature value in Celsius (i.e. a 

value “22” in the Modbus register must be interpreted a

s 22ºC) 

 

 

Decicelsius  value

:  Value  in  Modbus  register  is  the  temperature  value  in 

decicelsius  (i.e.  a  value  “220”  in  the  Modbus  register  must  be  interpreted  as 

22.0ºC) 

 

 

Fahrenheit  value

:  Value  in  Modbus  register  is  the  temperature  value  in 

Fahrenheit  (i.e.  a  valu

e  “72”  in  the  Modbus  register  must  be  interpreted  as  72ºF 

(~22ºC). 

 

4.2.9

 

Zones 

 

Zone x setup 

Zone1 (Prot Add 83) 
Zone2 (Prot Add 84)

 

Zone x temp. set. mode 

Zone1 (Prot Add 16) 
Zone2 (Prot Add 17)

 

Operation 

Mode 

(Prot Addr 4) 

Zone x set. temp. 

Zone1 (Prot Add 12) 
Zone2 (Prot Add 13)

 

Zone x current temp 

Zone 1 (Prot Add 14) 
Zone 2 (Prot Add 15)

 

1: Room 

1: Room temperature 

1: Heat 
2: Heat Tank 
3: Tank 
4: Cool Tank 
5: Cool 

Room 

Room 

2: Compensation Curve 

Water Shift 

Water 

3: Direct 

Water 

2: Pool 

4: Pool Temp 

1: Heat 
2: Heat Tank 

Pool 

Pool 

Содержание INTESIS INMBSPAN001A000

Страница 1: ...Modbus RTU EIA 485 Interface for Panasonic Air to Water systems Compatible with Panasonic Aquarea H generation models USER MANUAL Issue date 05 2020 r1 3 ENGLISH...

Страница 2: ...ll rights reserved This information is subject to change without notice URL https www intesis com 2 22 Modbus RTU EIA 485 Interface for Panasonic Air to Water systems Compatible with Panasonic Aquarea...

Страница 3: ...nd are only intended to help improve understanding of the functionality and handling of the product In view of the wide range of possible applications of the product and because of the many variables...

Страница 4: ...fication 8 4 1 Modbus physical layer 8 4 2 Modbus Registers 8 4 2 1 General System Control 8 4 2 2 Zones 9 4 2 3 Tank Configuration 10 4 2 4 Consumption 11 4 2 5 Maintenance 11 4 2 6 Unit Configuratio...

Страница 5: ...Direct connection to Modbus RTU EIA 485 networks Up to 63 INMBSPAN001A000 devices can be connected in the same network INMBSPAN001A000 is a Modbus slave device Direct connection to the Hydro unit Up...

Страница 6: ...ered part to the socket CN CNT of the Hydro unit s electronic circuit You can place the INMBSPAN001A000 inside or outside the Hydro unit depending on your needs Remember that the INMBSPAN001A000 must...

Страница 7: ...ing the instructions of the diagram above 4 Connect the EIA 485 bus to the connector EIA485 of the interface 5 Close the Hydro indoor unit 6 Check the DIP Switch configuration of the Intesis interface...

Страница 8: ...and they use the standard Modbus big endian notation 4 2 1 General System Control Register Address protocol address Register Address PLC address R W Description 0 1 R W System On Off 0 Off 1 On Defau...

Страница 9: ...3 Internal room sensor 4 Room thermistor 5 Pool Sensor 12 13 R W Zone 1 setpoint temperature 3 4 COOL Water shift 5 5 C C x10 C 41 41 F Water 5 20 C C x10 C 41 68 F Room 18 35 C C x10 C 64 4 95 F HEAT...

Страница 10: ...emperature setting mode 3 4 1 Room temperature 2 Compensation curve Water Temp 3 Direct Water Temp 4 Pool Temp 18 19 R Zone 1 min Setpoint temperature 1 3 Any C x10 C 19 20 R Zone 1 max Setpoint tempe...

Страница 11: ...intenance Register Address protocol address Register Address PLC address R W Description 52 53 R Error Code 5 0 No Error 0xxx U err 1xxx H err 2xxx F err 64 65 R Device Status 1 Off 2 On 70 71 R Curre...

Страница 12: ...re s values temperature registers are expressed according to the temperature s format configured through its onboard DIP Switches See 4 3 DIP switch Configuration Interface These following formats are...

Страница 13: ...lease check the Hydro Unit User s Manual for more information about the zones configuration and their options 4 3 DIP switch Configuration Interface All the configuration values on INMBSPAN001A000 can...

Страница 14: ...d not used Reserved not used Default value Reserved not used Table 4 1 SW1 Hydro unit s features SW3 SW4 Baud rate configuration SW3 P7 8 SW4 P3 Description 2400bps 4800bps 9600bps Default value 19200...

Страница 15: ...cription Temperature values in Modbus register are represented in degrees x1 Default value Temperature values in Modbus register are represented in decidegrees x10 Temperature values in Modbus registe...

Страница 16: ...s Add SW3 P1 6 Add SW3 P1 6 Add SW3 P1 6 Add SW3 P1 6 Add SW3 P1 6 0 13 26 39 52 1 14 27 40 53 2 15 28 41 54 3 16 29 42 55 4 17 30 43 56 5 18 31 44 57 6 19 32 45 58 7 20 33 46 59 8 21 34 47 60 9 22 35...

Страница 17: ...s be 1 when this function is being used in case of writing 4 5 Device LED indicator The device includes two LED indicators to show all the possible operational states In the following table there are...

Страница 18: ...transmitters outputs are in three state high impedance it is also required a fail safe biasing mechanism This mechanism provides a safe status a correct voltage level in the bus when all the transmit...

Страница 19: ...s For terminal solid wires or stranded wires twisted or with ferrule 1 core 0 5mm2 2 5mm2 2 cores 0 5mm2 1 5mm2 3 cores not permitted Stock Humidity 95 RH non condensing Modbus RTU port 1 x Serial EIA...

Страница 20: ...tion is subject to change without notice URL https www intesis com 20 22 6 List of supported Hydro Unit Types A list of Panasonic Hydro unit model s references compatible with INMBSPAN001A000 and thei...

Страница 21: ...emperature control 176 H76 Indoor control panel communication abnormality 190 H90 Indoor outdoor abnormal communication 191 H91 Tank heater OLP abnormality 195 H95 Indoor Outdoor wrong connection 198...

Страница 22: ...change without notice URL https www intesis com 22 22 Error Code Modbus Error in Remote Controller Error Description 249 F49 Outdoor bypass outlet temperature sensor abnormality 295 F95 Cooling high...

Отзывы: