Intesis
TM
INMBSPAN001A000
User’s Manual r1.
3 EN
© HMS Industrial Networks S.L.U. - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
11 / 22
4.2.4
Consumption
Register Address
(protocol address)
Register Address
(PLC address)
R/W Description
45
46
R
Tank mode energy consumption
▪
0..50.800 W
46
47
R
Heat mode energy consumption
▪
0..50.800 W
47
48
R
Cool mode energy consumption
▪
0..50.800 W
4.2.5
Maintenance
Register Address
(protocol address)
Register Address
(PLC address)
R/W Description
52
53
R
Error Code
5
▪
0: No Error
▪
0xxx: U+err
▪
1xxx: H+err
▪
2xxx: F+err
64
65
R
Device Status
▪
1: Off
▪
2: On
70
71
R
Current error status
▪
0: No error
▪
1: Error
4.2.6
Unit Configuration
Register Address
(protocol address)
Register Address
(PLC address)
R/W Description
81
82
R
▪
0: No
▪
1: Yes
82
83
R
Number of zones
▪
1: 1 zone
▪
2: 2 zones
83
84
R
Zone 1 setup
▪
1: Room
▪
2: Pool
84
85
R
▪
1: Room
▪
2: Pool
85
86
R
Direction
▪
1: Room
▪
2: Tank
86
87
R
Outdoor type
▪
1: STD
▪
2: TCAP
▪
3: HWT
5
See section 7 for possible error codes and their explanation