3.
Connections
Find below information regarding the Intesis connections available.
Power Supply
Must use NEC Class 2 or Limited Power Source (LPS) and
SELV
rated power supply.
If using DC power supply:
Respect polarity applied of terminals (+) and (-). Be sure the
voltage applied is within the range admitted (check table below).
The power supply can be connected to earth but only through
the negative terminal, never through the positive terminal.
If using AC power supply:
Make sure the voltage applied is of the value admitted (24 Vac).
Do not connect any of the terminals of the AC power supply to
earth, and make sure the same power supply is not supplying
any other device.
Ethernet / Home Automation (WMP) / Console (UDP & TCP)
Connect the cable coming from the IP network to the connector
ETH of the gateway. Use an Ethernet CAT5 cable. If
communicating through the LAN of the building, contact the
network administrator and make sure traffic on the port used is
allowed through all the LAN path (check the gateway user
manual for more information). Default IP is 192.168.100.246.
DHCP is enabled by default.
PortA / H-Link Hisense
Connect the H-Link terminals (TB2) of Hisense Outdoor Unit to
the connectors A3 and A4 of gateway’s PortA.
There is no polarity to be respected.
PortB / Free
Console Port
Connect a mini-type B USB cable from your computer to the gateway to allow communication between the
Configuration Software and the gateway. Remember that Ethernet connection is also allowed. Check the user
manual for more information.
USB
Connect a USB storage device (not HDD) if required. Check the user manual for more information.
Ensure proper space for all connectors when mounted (see
Home
Automation
(WMP)
Hisense
H-Link
TB2