Transmission
Abnormality between Outdoor and
Outdoor
lncorrect Wiring
,
Breaking Wire
,
Loose
Terminals
0b
Outdoor Unit
lncorrect Outdoor Unit Address
Setting
Duplication of Address
Setting for Outdoor Units
(Sub Units) in Same
Refrigerant! Cycle System
0c
lncorrect Outdoor Unit Main Unit
Setting
Two (or more) Outdoor Units
Set as
"M
ain Unit
"
Exist in
Same Refrigerant! Cycle
System
11
Sensoron
lndoor Unit
lnlet Air Thermistor
lncorrect Wiring
,
Disconnecting Wiring
Breaking Wire, Short
Circuit
12
Outlet Air Thermistor
13
Freeze Protection Thermistor
14
Gas Piping Thermistor
19
Fan Motor
Activation of Protection Device for
lndoor Fan
Fan Motor Overheat
,
Locking
21
Sensor on
Outdoor Unit
High Pressure Sensor
lncorrect Wiring
,
Disconnecting Wiring
Breaking Wire
,
Short
Circuit
22
Outdoor Air Thermistor
23
Discharge Gas Thermistor on Top of
Compressor
24
Heat Exchanger Liquid Pipe Thermistor
25
Heat Exchanger Gas Pipe Thermistor
29
Low Pressure Sensor
31
System
lncorrect Capacity Setting of Outdoor
Unit and lndoor Unit
lncorrect Capacity Code Setting of
Combination Excessive or lnsufficient
lndoor Unit Total Capacity Code
35
lncorrect Setting of lndoor Unit No.
Duplication of lndoor Unit No. in same Ref.
Gr.
36
lncorrect of lndoor Unit Combination
lndoor Unit is Designed for R22
38
Abnormality of Picking up Circuit for
Protection in Outdoor Unit
Failure of Protection Detecting Device
(lncorrect Wiring of Outdoor PCB)
39
Compressor
Abnormality Running Current at
Constant! Speed Compressor
Overcurrent, Blowout Fuse, Current Sensor
Failure, instantaneous Power Failure,
Voltage Drop, Abnormal Power Supply
3A
Outdoor Unit
Abnormality of Outdoor Unit Capacity
Outdoor Unit Capacity > 510kBtu/h
3b
lncorrect Setting of Outdoor Unit
Models Combination or Voltage
lncorrect Setting of Main and Sub Unit(s)
Combination or Voltage
3d
Abnormality Transmission between
Main Unit and Sub Unit(s)
lncorrect Wiring, Disconnect Wire, Breaking
Wire, PCB Failure
Activation of Low Compression Ratio
Protection Device
Defective Compression (Failure of
Compressor of lnverter, Loose Power