71
PMML0600 rev.0 - 06/2022
6
OP
TIONAL UNIT WIRING F
OR A
CCES
SORIES
ELEC
TRICAL AND C
ONTROL SETTINGS
Thermostat requirements:
Power supply: 230V AC
Contact voltage: 230V
13
14
13
14
Jumper
Common
Line
Demand ON/OFF Receiver input 2
NOTE
•
If wireless intelligent thermostat is selected, optional ON/OFF thermostat has no effect.
•
Set the configuration in the user’s control.
•
In case of setting an installation with 2 circuits (Circuit 1 and Circuit 2) and a different Demand
ON/OFF is used for each of them, please refer to
“6.1.2 Input terminals (Default input functions)”
section in this chapter.
•
Auxiliary power supply is available for thermostats and central devices (28 and 29 terminals of
TB2).
◆
Unit controller connection
In those cases where the unit controller is ordered as a required accessory, or those cases where
another unit controller must be connected as a second thermostat, the connections between
unit controlelr and the indoor unit must be done in terminals 3 and 4, as it is shown in the next
picture:
3
4
A
B
RCS H-LINK
OK