29
PMML0600 rev.0 - 06/2022
3
CONSIDERA
TIONS
ELEC
TRICAL D
AT
A
3.1.2 Hydrosplit system - Outdoor unit
3.1.2.1 RAS-(4-7)(V)WR1E in combination with YUTAKI H, YUTAKI H Combi
Model
Power supply
Applicable voltage
Compressor and fan motors
MC
(A)
Max. IPT
(kW)
Cooling
Heating
U max.
(V)
U min.
(V)
RNC
(A)
IPT
(KW)
RNC
(A)
IPT
(KW)
RASM-4VRW1E
~ 230V 50Hz
253
207
14.3
3.26
10.3
2.34
28.5
5.90
RASM-5VRW1E
16.0
3.65
11.7
2.67
28.5
5.90
RASM-6VRW1E
17.7
4.04
12.7
2.89
28.5
5.90
RASM-4RW1E
3N~ 400V 50Hz
440
360
5.2
3.26
3.8
2.34
16.0
9.10
RASM-5RW1E
5.8
3.65
4.3
2.67
16.0
9.10
RASM-6RW1E
6.5
4.04
4.6
2.89
16.0
9.10
RASM-7RW1E
7.2
4.46
5.8
3.62
16.0
9.10
3.1.3 Hydrosplit system - Indoor unit
3.1.3.1 YUTAKI H
HWM-WE
Model
Power supply
Applicable voltage
Operation mode
RNC
(A)
IPT
(kW)
MC
(A)
Max.
IPT
(kW)
U max.
(V)
U min.
(V)
HWM-WE
~ 230V 50Hz
253
207
Without electric heater
1.4
0.18 1.47 0.18
With electric heater
27.6 6.18 27.6 6.18
With DHW tank heater
14.5 3.18 14.5 3.18
With DHW tank heater and
electric heaters
40.6 9.18 40.6 9.18
3N~ 400V 50Hz
440
360
Without electric heater
1.4
0.18 1.47 0.18
With electric heater
9.6
6.18 10.1 6.18
With DHW tank heater
4.8
3.18 14.5 3.18
With DHW tank heater and
electric heaters
13.7 9.18 23.2 9.18
NOTE
The data corresponding to DHW tank heater is calculated in combination with the domestic hot
water tank accessory “DHWT‑(200/300)S‑3.0H2E”.