Heating circuit examples – 3
*HC1 pump
must
be powered from X1 if no buffer tank is fitted
2 circuit – 1 mixed (essential settings)
Parameter
Description
Menu
P101
HC1 type 1 (mixing)
03>01
P201
HC2 type 1 (direct)
03>02
P102
HC1 OTC heating curve (set as required for system and building type)
04>01>00
P103
HC1 emitter type 0= UFH, 1=Radiator, 2=Convector
04>01>01
P202
HC2 OTC heating curve (set as required for system and building type)
04>02>00
P203
HC2 emitter type 0= UFH, 1=Radiator, 2=Convector
04>02>01
System Configuration (other settings)
P104
HC1 Room compensation settings
04>01>02
P105, P106
HC1 minimum and maximum supply set-points
04>01>03-04
P108
Mixing valve running time (see manufacturers data)
04>01>06
P204
HC2 Room compensation settings
04>02>02
P205, P206
HC2 minimum and maximum supply set-points
04>02>03-04
P208
Mixing valve running time (see manufacturers data)
04>02>06
Inputs to system controller
U1
System flow sensor (See Configuration drawing)
Extra Low voltage
U2
Heating Circuit 1 flow sensor
Extra Low voltage
Outputs from system controller
X1
Heating circuit 1 circulation pump (alternatively powered from local heating
system, see text)
230 Volts
X2:X3
Heating circuit 1 mixing valve
230 Volts
X4
Heating circuit 2 circulation pump (alternatively powered from local heating
system, see text)
230 Volts