![Hitachi RHUE-3AVHN-HM Скачать руководство пользователя страница 13](http://html.mh-extra.com/html/hitachi/rhue-3avhn-hm/rhue-3avhn-hm_installation-and-reference-manual_2139385013.webp)
Page
13
of
61
Transportation
The heat pump must be transported in its original packaging in an upright position only.
If lifted by hoist or crane observe the following precautions.
•
Use suitable wire lifting ropes only
•
Protect the unit against abrasion from the lifting ropes
•
Lift smoothly
•
When handling manually, ensure adequate personal are involved to prevent damage or injury.
•
Do not remove wooden base from unit until final installation
•
Always lift using suitable slings
•
The Centre of gravity of single fan units is 440mm from base of heat pump
•
The Centre of gravity of twin fan units is around 550mm from base of heat pump
•
See the service manual Page 12 for greater detail of weight distribution
Installation space
Sufficient space shall be provided around the heat pump to allow fresh clean air to be drawn from the
rear of the unit, through the fan(s) and expelled safely from the front. Cold air expressed from the front
of the unit must not be allowed to re-circulate to the rear of the unit. Access must be made available
from the sides and above the unit for maintenance purposes.
A minimum space of 200mm must be left between rear of the heat pump and the nearest wall. Ideally
this distance will be greater than 200mm in order to allow sufficient access for maintenance of the unit.
Any roof or structure connected to the rear wall shall be at least 1000mm above the heat pump.