Heating circuit example 2
Single circuit unmixed (essential settings)
Parameter
Description
Menu
P101
Heating circuit 1 type 0 (direct)
03>01
P102
HC1 OTC heating curve (set as required for system and building type)
04>01>00
P103
HC1 Heating system emitter type 0= UFH, 1=Radiator, 2=Convector
04>01>01
System Configuration (other settings)
P104
HC1 Room compensation settings
04>01>02
P105, P106
HC1 minimum and maximum supply set-points
04>01>03-04
P108
Mixing valve running time (see manufacturers data)
04>01>06
Inputs to system controller
U1
System supply temperature sensor
(See configuration drawing for position)
Extra Low voltage
Outputs from system controller
X1
Heating circuit 1 circulation pump
230 Volts