All external pipe-work, valves and fittings must be properly fixed, soundly insulated and weather proof.
Identification of flow and return pipe-work and accessibility of strainer and isolation valves is essential
for ease of maintenance.
All pipe-work from the heat pump to the system components (Hydraulic separator, DHW cylinder, Buffer
tank etc.) must be 28mm copper in order to minimise pressure drop and maintain system efficiency
under worst case operating conditions. All remaining pipe-work shall be selected and sized according to
system design considerations as set out in this document, local requirements and regulations in force at
the time of installation.
Sensors must make a mechanically sound and thermally efficient connection to pipe-work and sensor
pockets. Use of thermal transfer (e.g. heat-sink) compound, mechanical fixings and aluminium tape are
recommended, surrounded by good quality thermal insulation.