29
TEST RUNNING
Table 4. Safety and Control Device Setting
Cooling Unit
Model
RAS-4U2S
RAS-5U2S
RAS-6U2S
RAS-8U2S
RAS-9U2S
RAS-10U2S
For Evaporator Fan Motor
Overcurrent Relay
A
Manual Reset, Adjustable
1.3
1.3
1.8
1.8
3.6
3.6
Condensing Unit
Models
RAS-
NP4CTS
RAS-
NP5CTS
RAS-
NP6CTS
RAS-
NP8CTS
RAS-
NP9CTS
RAS-
NP10CTS
RAS-
NP13CTS
RAS-
NP15CTS
For Compressor
E406DH E506DH E626DH E856DH
E506DH /
E406DH
E506DH
E856DH /
E506DH
E856DH
High Pressure switch
Automatic Reset, Non-Adjustable
Cut-Out
Cut-In
MPa
kg/cm
2
G
MPa
kg/cm
2
G
4.15
42.3
3.2
32.6
4.15
42.3
3.2
32.6
4.15
42.3
3.2
32.6
4.15
42.3
3.2
32.6
4.15
42.3
3.2
32.6
4.15
42.3
3.2
32.6
4.15
42.3
3.2
32.6
4.15
42.3
3.2
32.6
Low Pressure switch
Automatic Reset, Non-Adjustable
Cut-Out
Cut-In
MPa
kg/cm
2
G
MPa
kg/cm
2
G
0.4
4.1
0.7
7.1
0.4
4.1
0.7
7.1
0.4
4.1
0.7
7.1
0.4
4.1
0.7
7.1
0.4
4.1
0.7
7.1
0.4
4.1
0.7
7.1
0.4
4.1
0.7
7.1
0.4
4.1
0.7
7.1
Overcurrent Transformer
Automatic Reset, Non-Adjustable
Cut-Out
A
8.3
10.6
13.0
18.0
8.3/10.6
10.6
18.0/10.6
18.0
Internal Thermostat
Automatic Reset, Non-Adjustable
Cut-Out
Cut-In
°C
°C
130
108
130
108
130
108
130
108
130
108
130
108
130
108
130
108
CCP Timer for Compressor
(built-in PCB)
Non-Adjustable
No.1
No.2
min
min
3
—
3
—
3
—
3
—
3
3.5
3
3.5
3
3.5
3
3.5
For Evaporator Fan motor
Overcurrent Relay
A
—
—
—
—
—
—
6.0
6.0
For Condenser Fan motor
Internal Thermostat
Automatic Reset, Non-Adjustable
Cut-Out
Cut-In
°C
°C
160
130
160
130
160
130
160
130
160
130
160
130
160
130
160
130
For Control Circuit Fuse
Capacity
A
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5