CONDENSATE DRAIN PIPING
Condensate Drain Piping
Tools and Instruments - General Piping Tools
Trap - A female piping thread screw connection is provided. Dimension “L” in Fig. 7. should be
sufficiently longer than the negative fan pressure at the drain connection (50 mm to 100 mm depends on
the return air duct design). Always fill the trap with water.
Fig. 7. Condensate Drain Connection
NOTE;
When the relative humidity of inlet air or ambient air exceeds 80
%
, apply an auxiliary drain pan
(field-supplied) beneath the cooling unit as shown in Fig. 7.
Field Insulation
Insulate the duct flange, the refrigerant piping connection and the condensate drain connection
adequately, as shown in Fig. 8.
* : Field-Supplied
Fig. 8. Field Insulation