– 66 –
No.
Blinking of Timer lamp
Reason for indication
Possible cause
Reversing valve defective
When the indoor heat exchanger
temperature is too low in the
heating mode or it is too high in the
cooling mode.
Outdoor unit is under forced
operation
When the outdoor unit is in forced
operation or balancing operation
after forced operation.
Indoor/outdoor interface defective
When the interface signal from the
outdoor unit is interrupted.
Room thermistor or heat exchanger
thermistor is faulty
When room thermistor or heat
exchanger thermistor is opened
circuit or short circuit.
Over-current detection at the DC fan
motor
when over-current is detected at the
DC fan motor of the indoor unit.
IC401 or IC402 data reading error
When data read from IC401 or
IC402 is incorrect.
(1) Reversing valve defective
(2) Heat exchanger thermistor
disconnected
(only in the heating mode)
(Note)
The malfunction mode is entered the
3rd time this abnormal indication
appears (read every 3 minutes).
Electrical parts in the outdoor unit
(1) Indoor interface circuit
(2) Outdoor interface circuit
(1) Room thermistor
(2) Heat exchanger thermistor
(1) Indoor fan locked
(2) Indoor fan motor
IC401 or IC402 abnormal
<Cautions>
(1)
If the interface circuit is faulty when power is supplied, the self-diagnosis display will not be displayed.
(2)
If the indoor unit does not operate at all, check if the connecting cable is connected to the outdoor unit.
(3)
To check operation again when the timer lamp is blinking, you can use the remote control for operation
(except for mode mark 1).
1
2
3
5
6
7
(
Lights for 0.35 sec. at interval of 0.35 sec.)
10 times
3 times
1 time
2 times
13 times
2 sec.
2 sec.
2 sec.
2 sec.
2 sec.
1
9 times
2 sec.
(3) Indoor control P.W.B.
Outdoor unit electrical components
defetive
When the same error mode is detected
8 times within 30 minutes from outdoor
unit electrical components.
(However, when error is detected 8
times within two hours only for outdoor
thermistor.)
Outdoor unit electrical components
(For details, operate again using
remote comtroller and check from
self-diagnosis display of outdoor
unit.)
4
4 times
2 sec.
TROUBLESHOOTING WHEN TIMER LAMP BLINKS.
Model RAS-E14H2A
Perform troubleshooting according to the number of times the indoor timer lamp and outdoor LD301
blink.
SELF-DIAGNOSIS LIGHTING MODE
Model: RAS-E14H2A
08A395_RAS_35YH6_061-082_E
2008.01.31, 10:16
66
Содержание RAC-E14H2
Страница 17: ... 15 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAS E14H2A 08A395_RAS_35YH6_015 018_E 2008 03 04 17 01 15 ...
Страница 22: ...RAS E14H2A CIRCUIT DIAGRAM 20 08A395_RAS_35YH6_020 021_A2_E 2008 03 05 16 03 20 ...
Страница 25: ... 23 button 25 26 26 27 28 26 RAS E14H2A Silent Silent Silent 08A395_RAS_35YH6_023_A3_E 2008 03 10 15 38 23 ...
Страница 92: ... 90 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAS E14H2A 08A395_RAS_35YH6_083 093_E 2008 03 10 15 50 90 ...
Страница 94: ...THE UPDATED PARTS LIST FOR THIS MODEL IS AVAILABLE ON ESTA 92 ...
Страница 95: ...HITACHI SM0027 RAS E14H2A RAC E14H2 ...