Notes:
(1)
Condition for entering into Cool Dashed mode. When fan set to “Hi” or “Auto mode” and temperature difference between indoor temperature and set temperature has a
corresponding compressor speed (calculated value in Table 2) larger than CMAX.
(2)
Cool Dashed will release when i) a maximum 25 minutes is lapsed and ii) room temperature is lower than set temperature –3
°
C (thermo off) and iii) when room temperature
has achieved setting temperature –1
°
C then maximum Cool Dashed time will be revised to 20 minutes. And iv) indoor fan is set to Lo and Med fan mode and v) change operation
mode.
(3)
During Cool Dashed operation, thermo off temperature is set temperature (with shift value) –3
°
C. After thermo off, operation continue in Fuzzy control mode.
(4)
Compressor minimum “ON” time and “OFF” time is 3 minutes.
(5)
During normal cooling mode, compressor maximum speed CMAX will maintain for 60 minutes if indoor temperature is lower than CLM XTP. No time constrain if indoor temperature
is higher than CLMXTP.
(6)
(7)
When fan is set to “Med”, compressor speed will be limited to CJKMAX.
(8)
When fan is set to “Lo”, compressor speed will be limited to CBEMAX.
(9)
When fan is set to “Silent”, compressor speed will be limited to CSZMAX.
(10) During Cool Dashed, when room temperature reaches set temperature –1
°
C compressor speed is actual speed x DWNRATEC.
Item
Temperature
Room
temperature
Outdoor
temperature
30°C
32°C
32°C
33°C
Thermo judgment (ON)
Thermo judgment (OFF)
Thermo judgment (ON)
Thermo judgment (OFF)
Table 1 Thermo judgment
When fan speed setting on remote control is “Hi” or “Auto” mode, and both room and outdoor temperatures (data based on out door unit) meet temperature judgment
(Off) shown in the table 1, the compressor speed will be limited to CKYMAX.
Table 2 Compressor speed
Calculated
compressor speed
2500 min
–1
2900 min
–1
3300 min
–1
3700 min
–1
4100 min
–1
4500 min
–1
4800 min
–1
E14H2A
Temperature
difference
1.66°C
2.00°C
2.33°C
2.66°C
3.00°C
3.33°C
3.66°C
(with shift value)
– 25 –
08A395_RAS_35YH6_025-028_A3_E
2008.03.10, 15:40
25
Содержание RAC-E14H2
Страница 17: ... 15 CONSTRUCTION AND DIMENSIONAL DIAGRAM MODEL RAS E14H2A 08A395_RAS_35YH6_015 018_E 2008 03 04 17 01 15 ...
Страница 22: ...RAS E14H2A CIRCUIT DIAGRAM 20 08A395_RAS_35YH6_020 021_A2_E 2008 03 05 16 03 20 ...
Страница 25: ... 23 button 25 26 26 27 28 26 RAS E14H2A Silent Silent Silent 08A395_RAS_35YH6_023_A3_E 2008 03 10 15 38 23 ...
Страница 92: ... 90 PARTS LIST AND DIAGRAM INDOOR UNIT MODEL RAS E14H2A 08A395_RAS_35YH6_083 093_E 2008 03 10 15 50 90 ...
Страница 94: ...THE UPDATED PARTS LIST FOR THIS MODEL IS AVAILABLE ON ESTA 92 ...
Страница 95: ...HITACHI SM0027 RAS E14H2A RAC E14H2 ...