48
HX-RIO3 Series
✓
Sub-function 0x0001(1) Restart Communications Option
The remote device could be initialized and restarted, and all of its communications event counters are
cleared. Especially, data field 0x55AA makes the remote device to restart with factory default setup of
EEPROM.
Sub-function
Data Field (Request)
Data
Field
(Response)
Description
0x0001(1)
0x0000, 0xFF00
Echo Request Data
Reset
0x0001(1)
0x55AA
Echo Request Data
Reset
with
Default
setting
1)
0x0001(1)
sumcheck
4)
Echo Request Data
Reset
with
Factory
Default
2)
0x0001(1)
sumcheck
4)
Echo Request Data
Reset
with
Factory
Default
3)
1),2),3)All expansion slot configuration parameters are cleared.
2),3) IP address, Subnet Mask Address, Gateway Address, RS232/485 setting, and BOOTP/DHCP mode will be the
factor default value
3)Mac address will be the factory default value
4)Refer the A.4.2 sum check(0x1006)
✓
Sub-function 0x000A(10) Clear Counters and Diagnostic Register
The goal is to clear all counters and the diagnostic register. Counters are also cleared upon power–up.
Sub-function
Data Field (Request)
Data Field (Response)
Description
0x000A(10)
0x0000
Echo Request Data
✓
Sub-function 0x000B(11) Return Bus Message Count
The response data field returns the quantity of messages that the remote device has detected on the
communications system since its last restart, clear counters operation, or power
–up.
Sub-function
Data Field (Request)
Data Field (Response)
Description
0x000B(11)
0x0000
Total Message Count
✓
Sub-function 0x000D(13) Return Bus Exception Error Count
The response data field returns the quantity of MODBUS exception responses returned by the remote
device since its last restart, clear counters operation, or power
–up.
Exception responses are described and listed in section 6.2.11.
Sub-function
Data Field (Request)
Data Field (Response)
Description
0x000D(13)
0x0000
Exception Error Count
✓
Sub-function 0x000E(14) Return Slave Message Count
The response data field returns the quantity of messages addressed to the remote device, or broadcast,
that the remote device has processed since its last restart, clear counters operation, or power
–up.
Sub-function
Data Field (Request)
Data Field (Response)
Description
0x000E(14)
0x0000
Slave Message Count
✓
Sub-function 0x000F(15) Return Slave No Response Count
The response data field returns the quantity of messages addressed to the remote device for which it has
returned no response
(neither a normal response nor an exception response),
since its last restart, clear counters
operation, or power
–up.
Sub-function
Data Field (Request)
Data Field (Response)
Description
0x000F(15)
0x0000
Slave
No
Response
Count
✓
Содержание HX-RIO3 Series
Страница 1: ...1 HX RIO3 Series Version 1 02 MODBUS Programmable I O RIO3 CP3MBT User Manual ...
Страница 2: ...2 HX RIO3 Series DOCUMENT CHANGE SUMMARY REV PAGE REMARKS DATE EDITOR 1 02 All new Jan 21 Faber ...
Страница 36: ...36 HX RIO3 Series 4 Search the file to download using a search button 5 Click a Upload Button ...
Страница 37: ...37 HX RIO3 Series 6 If it finish you can see a below message File Upload Done And click a Reset Adapter button ...