3.1. General Specification
General Specification
UL System Power
Supply Voltage : 24Vdc nominal, Class 2
System Power
Supply Voltage : 24Vdc nominal
Supply Voltage range : 15~30Vdc
Protection : Output current limit (Min. 1.5A) Reverse polarity protection
Power Dissipation
110mA typical @ 24Vdc
Current for I/O Module
1.5A @5Vdc
Isolation
System Power to internal logic : Non-Isolation
System Power I/O driver : Isolation
Field Power
Supply Voltage : 24Vdc typical (Max. 30Vdc)
*Field Power Range is different depending on IO Module series.
Refer to IO Module`s Specification.
Max. Current Field Power Contact DC 10A Max.
Wiring
I/O Cable Max. 2.0mm2(AWG 14)
Weight
<167g
Module Size
54mm x 99mm x 70mm
Environment Condition
Operating Temperature
-20
℃
~ 60
℃
UL Temperature
-20
℃
~ 60
℃
Storage Temperature
-40
℃
~ 85
℃
Relative Humidity
5% ~ 90% non-condensing
Mounting
DIN rail
Shock Operating
IEC 60068-2-6
Vibration/shock resistance
Based on IEC 60068-2-6
Sine Vibration
- 10 ~ 25 Hz : 0.5mm
- 50 ~ 150 Hz : 5g
- 150 ~ 1000 Hz : 2g
- Sweep Rate : 1 Oct/min, 50 cycles
Sine Vibration
- 10 ~ 25 Hz : 0.03 g²/Hz
- 25 ~ 50 Hz : 0.05 g²/Hz
- 50 ~ 150 Hz : 0.15 g²/Hz
- 150 ~ 1000 Hz : 0.01 g²/Hz
EMC resistance burst/ESD
IEC 60068-2-27
EN 61000-6-2 : 2005
EN 61000-6-4/ALL : 2011
Installation Pos. / Protect. Class
Variable / IP20
Product Certifications
UL, CE, RoHS2
Содержание HX-RIO3 Series
Страница 1: ...1 HX RIO3 Series Version 1 02 MODBUS Programmable I O RIO3 CP3MBT User Manual ...
Страница 2: ...2 HX RIO3 Series DOCUMENT CHANGE SUMMARY REV PAGE REMARKS DATE EDITOR 1 02 All new Jan 21 Faber ...
Страница 36: ...36 HX RIO3 Series 4 Search the file to download using a search button 5 Click a Upload Button ...
Страница 37: ...37 HX RIO3 Series 6 If it finish you can see a below message File Upload Done And click a Reset Adapter button ...