Replacing cache memory
9–7
Hitachi Unified Storage Hardware Service Guide
Figure 9-4: Controller LEDs on a CBL
9. Push the controller all the way into the slot, with its right and left levers
open completely.
10.Push the levers at the same time in the direction shown by the arrows
(
←⎯
) at the same time. Otherwise, the controller might not recover and
you will have to repeat the replacement procedure.
11.Close the levers and slide the right and left blue latches to secure the
controller.
12.Replace all of the cables you removed from the controller.
13.Confirm the status of the following LEDs:
- Red
ALM LED on the controller is OFF.
- Orange
WARNING LED on the front bezel is OFF. If this LED blinks
slowly, visit the HDS Support Portal at
- Green
READY LED on the front of the Controller Box is ON. This
LED might blink quickly for 40-to-60 minutes or 80-to-180 minutes
when the DBW is connected to the CBL before the LED goes ON
before the LED goes ON.
14.In Storage Navigator Modular 2, check the recovery after replacing
components (see
Checking recovery after replacing components on
).
ALM LED
(red/orange)
RST SW
C-PWR LED (green)
NOTE: When connecting the Fibre Channel interface cables, insert the
cables until they are secure with the host connectors. If the cables are
inserted half into the host connectors, the controller continues to detect the
Fibre Channel failures and I/O processing may deteriorate.
NOTE: The controller usually recovers in about three minutes; however, if
I/O from the host is high, it may take up to 30 minutes to recover.
Содержание CBL
Страница 12: ...xii Hitachi Unified Storage Hardware Service Guide Serial Numbers Hitachi Unified Storage Models 110 and 130 ...
Страница 13: ...xiii Hitachi Unified Storage Hardware Service Guide Labels on the CBXSS Either a or b is affixed ...
Страница 14: ...xiv Hitachi Unified Storage Hardware Service Guide Labels on the CBXSL Either a or b is affixed a b ...
Страница 15: ...xv Hitachi Unified Storage Hardware Service Guide Labels on the CBSS Either a or b is affixed a b ...
Страница 16: ...xvi Hitachi Unified Storage Hardware Service Guide Labels on the CBSL Either a or b is affixed a b ...
Страница 17: ...xvii Hitachi Unified Storage Hardware Service Guide Labels on the CBL CBLE CBLD Either a or b is affixed a b ...
Страница 18: ...xviii Hitachi Unified Storage Hardware Service Guide Labels on the DBS DBSD Either a or b is affixed a b ...
Страница 19: ...xix Hitachi Unified Storage Hardware Service Guide Labels on the DBL DBLD Either a or b is affixed a b ...
Страница 20: ...xx Hitachi Unified Storage Hardware Service Guide Labels on the CBXSS ...
Страница 21: ...xxi Hitachi Unified Storage Hardware Service Guide Labels on the DBF Either a or b is affixed a b ...
Страница 22: ...xxii Hitachi Unified Storage Hardware Service Guide Labels on the DBX Either a or b is affixed kg a b a b ...
Страница 23: ...xxiii Hitachi Unified Storage Hardware Service Guide Labels on front of the DBW added on April 2014 ...
Страница 25: ...xxv Hitachi Unified Storage Hardware Service Guide Labels on rear of the DBW added on April 2014 ...
Страница 28: ...xxviii Hitachi Unified Storage Hardware Service Guide DBX DBW Labels on cache backup battery CBL CBLE CBLD ...
Страница 30: ...xxx Hitachi Unified Storage Hardware Service Guide CBL CBLE CBLD DBS DBSD DBL DBLD DBF ...
Страница 35: ...xxxv Hitachi Unified Storage Hardware Service Guide Labels on Management Module CBL CBLE CBLD LAN UPS ...
Страница 36: ...xxxvi Hitachi Unified Storage Hardware Service Guide Labels on I O Module ENC DBS DBSD DBL DBLD DBF ...
Страница 37: ...xxxvii Hitachi Unified Storage Hardware Service Guide DBW Labels on I O Card ENC DBX Labels on Host Connector ...
Страница 38: ...xxxviii Hitachi Unified Storage Hardware Service Guide Labels on SAS ENC Cable Labels on cable holder DBX In ...
Страница 39: ...xxxix Hitachi Unified Storage Hardware Service Guide Out ...
Страница 40: ...xl Hitachi Unified Storage Hardware Service Guide ...
Страница 126: ...3 8 Procedures before and after replacing components Hitachi Unified Storage Hardware Service Guide ...
Страница 152: ...5 8 Replacing a cache backup battery Hitachi Unified Storage Hardware Service Guide ...
Страница 156: ...6 4 Replacing a Fan Module Hitachi Unified Storage Hardware Service Guide ...
Страница 180: ...8 16 Adding and replacing controllers Hitachi Unified Storage Hardware Service Guide ...
Страница 188: ...9 8 Replacing cache memory Hitachi Unified Storage Hardware Service Guide ...
Страница 200: ...11 6 Replacing the Host connector Hitachi Unified Storage Hardware Service Guide ...
Страница 204: ...12 4 Replacing the Drive I O Module Hitachi Unified Storage Hardware Service Guide ...
Страница 212: ...14 4 Replacing the SAS ENC cable Hitachi Unified Storage Hardware Service Guide ...
Страница 274: ...17 14 Troubleshooting Hitachi Unified Storage Hardware Service Guide ...
Страница 286: ...Glossary 12 Hitachi Unified Storage Hardware Service Guide A B C D E F G H I J K L M N O P Q R S T U V W X Y Z ...
Страница 290: ...Index 4 Hitachi Unified Storage Hardware Service Guide U Upgrading Hitachi Unified Storage 130 15 1 ...
Страница 291: ...1 Hitachi Unified Storage Hardware Service Guide ...