8–12
Adding and replacing controllers
Hitachi Unified Storage Hardware Service Guide
Figure 8-5: Installing cache memory on a CBL
Installing the new controller
Confirm that at least 30 seconds have elapsed since you removed the old
controller. Then install the new controller into the storage system;
otherwise, the new controller might not recover. Ignore the red ALM LED if
it is ON after you insert the new controller; it will go OFF after the controller
recovers.
1. Push the controller all the way into the slot, with its right and left levers
open completely.
2. Push the levers at the same time in the direction shown by the arrows
(
←⎯
) at the same time. Otherwise, the controller might not recover and
you will have to repeat the replacement procedure.
3. Close the levers and slide the right and left blue latches to secure the
controller.
4. Be sure the orange WARNING LED on the front bezel is OFF. The
controller usually recovers in about three minutes; however, if I/O from
the host computer is high, it might take about 30 minutes to recover. If
this LED blinks slowly, visit the HDS Support Portal at
.
5. Confirm that the green READY LED on the front of the controller is ON.
This LED might blink quickly for 40-to-60 minutes or 80-to-180 minutes
when the DBW is connected to the CBL before the LED goes ON.
Slot
lever
Slot
Projections
inside the
slot
Cut
Slot #0
(CMM0)
Slot #1
(CMM1)
Cache
Memory
Controller #1
Lever
Lever
Latch (blue)
Latch
(blue)
Controller #0
Fan
Latch
Screw
(blue)
Module Revision Label
Содержание CBL
Страница 12: ...xii Hitachi Unified Storage Hardware Service Guide Serial Numbers Hitachi Unified Storage Models 110 and 130 ...
Страница 13: ...xiii Hitachi Unified Storage Hardware Service Guide Labels on the CBXSS Either a or b is affixed ...
Страница 14: ...xiv Hitachi Unified Storage Hardware Service Guide Labels on the CBXSL Either a or b is affixed a b ...
Страница 15: ...xv Hitachi Unified Storage Hardware Service Guide Labels on the CBSS Either a or b is affixed a b ...
Страница 16: ...xvi Hitachi Unified Storage Hardware Service Guide Labels on the CBSL Either a or b is affixed a b ...
Страница 17: ...xvii Hitachi Unified Storage Hardware Service Guide Labels on the CBL CBLE CBLD Either a or b is affixed a b ...
Страница 18: ...xviii Hitachi Unified Storage Hardware Service Guide Labels on the DBS DBSD Either a or b is affixed a b ...
Страница 19: ...xix Hitachi Unified Storage Hardware Service Guide Labels on the DBL DBLD Either a or b is affixed a b ...
Страница 20: ...xx Hitachi Unified Storage Hardware Service Guide Labels on the CBXSS ...
Страница 21: ...xxi Hitachi Unified Storage Hardware Service Guide Labels on the DBF Either a or b is affixed a b ...
Страница 22: ...xxii Hitachi Unified Storage Hardware Service Guide Labels on the DBX Either a or b is affixed kg a b a b ...
Страница 23: ...xxiii Hitachi Unified Storage Hardware Service Guide Labels on front of the DBW added on April 2014 ...
Страница 25: ...xxv Hitachi Unified Storage Hardware Service Guide Labels on rear of the DBW added on April 2014 ...
Страница 28: ...xxviii Hitachi Unified Storage Hardware Service Guide DBX DBW Labels on cache backup battery CBL CBLE CBLD ...
Страница 30: ...xxx Hitachi Unified Storage Hardware Service Guide CBL CBLE CBLD DBS DBSD DBL DBLD DBF ...
Страница 35: ...xxxv Hitachi Unified Storage Hardware Service Guide Labels on Management Module CBL CBLE CBLD LAN UPS ...
Страница 36: ...xxxvi Hitachi Unified Storage Hardware Service Guide Labels on I O Module ENC DBS DBSD DBL DBLD DBF ...
Страница 37: ...xxxvii Hitachi Unified Storage Hardware Service Guide DBW Labels on I O Card ENC DBX Labels on Host Connector ...
Страница 38: ...xxxviii Hitachi Unified Storage Hardware Service Guide Labels on SAS ENC Cable Labels on cable holder DBX In ...
Страница 39: ...xxxix Hitachi Unified Storage Hardware Service Guide Out ...
Страница 40: ...xl Hitachi Unified Storage Hardware Service Guide ...
Страница 126: ...3 8 Procedures before and after replacing components Hitachi Unified Storage Hardware Service Guide ...
Страница 152: ...5 8 Replacing a cache backup battery Hitachi Unified Storage Hardware Service Guide ...
Страница 156: ...6 4 Replacing a Fan Module Hitachi Unified Storage Hardware Service Guide ...
Страница 180: ...8 16 Adding and replacing controllers Hitachi Unified Storage Hardware Service Guide ...
Страница 188: ...9 8 Replacing cache memory Hitachi Unified Storage Hardware Service Guide ...
Страница 200: ...11 6 Replacing the Host connector Hitachi Unified Storage Hardware Service Guide ...
Страница 204: ...12 4 Replacing the Drive I O Module Hitachi Unified Storage Hardware Service Guide ...
Страница 212: ...14 4 Replacing the SAS ENC cable Hitachi Unified Storage Hardware Service Guide ...
Страница 274: ...17 14 Troubleshooting Hitachi Unified Storage Hardware Service Guide ...
Страница 286: ...Glossary 12 Hitachi Unified Storage Hardware Service Guide A B C D E F G H I J K L M N O P Q R S T U V W X Y Z ...
Страница 290: ...Index 4 Hitachi Unified Storage Hardware Service Guide U Upgrading Hitachi Unified Storage 130 15 1 ...
Страница 291: ...1 Hitachi Unified Storage Hardware Service Guide ...