8–2
Adding and replacing controllers
Hitachi Unified Storage Hardware Service Guide
Precautions when adding or replacing a controller
Observe the following guidelines when adding or replacing a controller.
• Avoid touching heat sinks or integrated circuits to avoid getting burned.
Handle all components with care.
• A controller can be replaced while the storage system is turned on. If
you will be replacing both controllers in a storage system, visit the HDS
Support Portal at
.
• To avoid electrostatic damage to the controller, wear a grounded wrist
strap any time you handle a controller. To discharge static electricity,
touch the metal plate on the controller.
• Avoid touching heat sinks and integrated circuits. Otherwise, you could
burn yourself.
• Do not install or replace a controller if the orange WARNING LED on
the front of the Controller Box blinks rapidly. This indicates that flash is
being updated or internal processing is occurring after a storage system
with a single controller has been turned on. Install or replace the
controller after the orange WARNING LED on the front of the
Controller Box goes OFF and the green READY LED goes ON (this can
take up to 85 minutes).
• If replacing a faulty controller, block the faulty controller to place it out
of service before replacing it.
• Complete the controller replacement within 10 minutes. Otherwise, an
abnormal rise in temperature can power off the storage system.
• If you replace a controller while the storage system is formatting a
volume, the time it takes to restore the new controller might be
delayed until the volume-formatting operation completes.
• If the ALM LED on the controller is ON while the ALM LED of the Fan
Module is ON, resolve the problem with the controller before resolving
the problem with the Fan Module.
• For storage systems that have the Power Saving/Power Saving Plus
option, removing and inserting a controller during drive spin-up might
prevent the controller from recovering fully. If this occurs, wait for all
the drives to spin up, and then remove the controller from the storage
system, wait at least 30 seconds, and reinsert it.
• Store the collected simple trace information on CD-R (see
trace information on page 3-13
).
Содержание CBL
Страница 12: ...xii Hitachi Unified Storage Hardware Service Guide Serial Numbers Hitachi Unified Storage Models 110 and 130 ...
Страница 13: ...xiii Hitachi Unified Storage Hardware Service Guide Labels on the CBXSS Either a or b is affixed ...
Страница 14: ...xiv Hitachi Unified Storage Hardware Service Guide Labels on the CBXSL Either a or b is affixed a b ...
Страница 15: ...xv Hitachi Unified Storage Hardware Service Guide Labels on the CBSS Either a or b is affixed a b ...
Страница 16: ...xvi Hitachi Unified Storage Hardware Service Guide Labels on the CBSL Either a or b is affixed a b ...
Страница 17: ...xvii Hitachi Unified Storage Hardware Service Guide Labels on the CBL CBLE CBLD Either a or b is affixed a b ...
Страница 18: ...xviii Hitachi Unified Storage Hardware Service Guide Labels on the DBS DBSD Either a or b is affixed a b ...
Страница 19: ...xix Hitachi Unified Storage Hardware Service Guide Labels on the DBL DBLD Either a or b is affixed a b ...
Страница 20: ...xx Hitachi Unified Storage Hardware Service Guide Labels on the CBXSS ...
Страница 21: ...xxi Hitachi Unified Storage Hardware Service Guide Labels on the DBF Either a or b is affixed a b ...
Страница 22: ...xxii Hitachi Unified Storage Hardware Service Guide Labels on the DBX Either a or b is affixed kg a b a b ...
Страница 23: ...xxiii Hitachi Unified Storage Hardware Service Guide Labels on front of the DBW added on April 2014 ...
Страница 25: ...xxv Hitachi Unified Storage Hardware Service Guide Labels on rear of the DBW added on April 2014 ...
Страница 28: ...xxviii Hitachi Unified Storage Hardware Service Guide DBX DBW Labels on cache backup battery CBL CBLE CBLD ...
Страница 30: ...xxx Hitachi Unified Storage Hardware Service Guide CBL CBLE CBLD DBS DBSD DBL DBLD DBF ...
Страница 35: ...xxxv Hitachi Unified Storage Hardware Service Guide Labels on Management Module CBL CBLE CBLD LAN UPS ...
Страница 36: ...xxxvi Hitachi Unified Storage Hardware Service Guide Labels on I O Module ENC DBS DBSD DBL DBLD DBF ...
Страница 37: ...xxxvii Hitachi Unified Storage Hardware Service Guide DBW Labels on I O Card ENC DBX Labels on Host Connector ...
Страница 38: ...xxxviii Hitachi Unified Storage Hardware Service Guide Labels on SAS ENC Cable Labels on cable holder DBX In ...
Страница 39: ...xxxix Hitachi Unified Storage Hardware Service Guide Out ...
Страница 40: ...xl Hitachi Unified Storage Hardware Service Guide ...
Страница 126: ...3 8 Procedures before and after replacing components Hitachi Unified Storage Hardware Service Guide ...
Страница 152: ...5 8 Replacing a cache backup battery Hitachi Unified Storage Hardware Service Guide ...
Страница 156: ...6 4 Replacing a Fan Module Hitachi Unified Storage Hardware Service Guide ...
Страница 180: ...8 16 Adding and replacing controllers Hitachi Unified Storage Hardware Service Guide ...
Страница 188: ...9 8 Replacing cache memory Hitachi Unified Storage Hardware Service Guide ...
Страница 200: ...11 6 Replacing the Host connector Hitachi Unified Storage Hardware Service Guide ...
Страница 204: ...12 4 Replacing the Drive I O Module Hitachi Unified Storage Hardware Service Guide ...
Страница 212: ...14 4 Replacing the SAS ENC cable Hitachi Unified Storage Hardware Service Guide ...
Страница 274: ...17 14 Troubleshooting Hitachi Unified Storage Hardware Service Guide ...
Страница 286: ...Glossary 12 Hitachi Unified Storage Hardware Service Guide A B C D E F G H I J K L M N O P Q R S T U V W X Y Z ...
Страница 290: ...Index 4 Hitachi Unified Storage Hardware Service Guide U Upgrading Hitachi Unified Storage 130 15 1 ...
Страница 291: ...1 Hitachi Unified Storage Hardware Service Guide ...