5.
.
Optional Setting and Input / Output Setting of Indoor Unit
A/C
SERV.
A/C
SERV.
ADDS RNkHR
FAN
FAN
A/C
SERV.
ADDS RNkHR
FAN
Normal Mode (When unit is not operating)
Change to the optional setting mode.
Press the “CHECK” switch and the ”RESET”
switch simultaneously for more than 3 seconds.
Selection of Optional Setting Mode
Press the "TEMP."
∨ or ∧
switch
and set “01” or “02”. Then press
the “CHECK” switch.
“SERV.” is
indicated and the
mode number is
flashed.
Selection of Indoor Unit for Optional Setting
"01" or "02" fashes.
Select the indoor unit to set by
pressing the “
∨
” or “
∧
” switch
and press the “CHECK” switch.
The address of the indoor unit
(ADDS) to set and the refrigerant
cycle number (RN) are indicated
by 0 to 15.(The left figure shows
the No.1 cycle and No.2 indoor unit.)
<Example>
When selecting No.2 cycle and
No.3 indoor unit
(The address is indicated by 0 to 15.)
NOTES: (1) In case that the both indications of the “ADDS.” and “RN” show “AA”,
the same setting is performed to all the indoor units.
(2) The address of indoor unit not connected is not indicated.
A/C
SERV.
FAN
FAN
A/C
SERV.
SERV.
A/C
FAN
A/C
SERV.
FAN
A/C
A/C
SERV.
FAN
SERV.
FAN
Optional Setting Mode (Mode Number “01”)
Selection of Optional Setting Items
Input / Output Setting Mode (Mode Number “02”)
Item Code of
Optional Setting
Select the item code
by pressing the
“TIME”
▽
or
△
switch.
<Example>
When selecting C5
(Increasing Fan
Speed)
In Case of Setting Other Items
Change of Setting Conditions
Setting Condition
The optional setting
condition is changed
by pressing
the “CHECK” switch.
<Example> When setting 01(Increasing Fan Speed 1)
Refer to the contents of the setting codes for the Table A of “Optional
Setting Items”.
Selection of Input / Output Number
Input / Output Number
Select the input /
output number by
pressing the “TIME”
▽
or
△
switch.
<Example>
When selecting o1
(Output 1)
Refer to Ta
�
le B (Page 8) for contents of the input / output
setting.
In Case of Setting Other Items
Change of Setting Conditions
Contents of
Input / Output Setting
The optional setting
condition is changed
(0→1→2→
…
) by
pressing the “CHECK”
switch.
<Example> When setting 04
(Output: Thermo-ON for Cooling)
Refer to the Table C for the contents of the input / output setting.
Normal Mode
Press the “RESET” switch in the condition of 4 or 5 to cancel the
optional setting mode.
Press
∨
or
∧
switch in step 4 or 5 when selecting
settings for another unit.
HYXE-F01H
21
Содержание HYE-W01
Страница 7: ......
Страница 9: ......
Страница 16: ...Model HYXE J01H Wired Remote Control Switch 7 ...
Страница 22: ...Model HYDE E01H 7 Day Timer 13 ...
Страница 24: ...Model HCCS H128H2C1YM HCCS H128H2C1NM Central Control 15 ...
Страница 25: ...Model HCCS H247R4C1E Central Control 16 ...
Страница 26: ...Model HYJ J01H Central Control 17 ...
Страница 27: ...Central Control Model HYJM S01H 18 ...
Страница 34: ...HYXE G01H 25 ...
Страница 35: ...HYXE G01H 26 ...
Страница 46: ...HYXE J01H 37 ...
Страница 47: ...HYXE J01H 38 ...
Страница 48: ...HYXE J01H 39 ...
Страница 49: ...HYXE J01H 40 ...
Страница 50: ...HYXE J01H 41 ...
Страница 51: ...HYXE J01H 42 ...
Страница 52: ...HYXE J01H 43 ...
Страница 53: ...HYXE J01H 44 ...
Страница 54: ...HYXE J01H 45 ...
Страница 55: ...HYXE J01H 46 ...
Страница 56: ...HYXE J01H 47 ...
Страница 57: ...HYXE J01H 48 ...
Страница 58: ...HYXE J01H 49 ...
Страница 59: ...HYXE J01H 50 ...
Страница 60: ...HYXE J01H 51 ...
Страница 61: ...HYXE J01H 52 ...
Страница 62: ...HYXE J01H 53 ...
Страница 63: ...HYXE J01H 54 ...
Страница 64: ...HYXE J01H 55 ...
Страница 65: ...HYXE J01H 56 ...
Страница 66: ...HYXE J01H 57 ...
Страница 67: ...HYXE J01H 58 ...
Страница 68: ...HYXE J01H 59 ...
Страница 69: ...HYXE J01H 60 ...
Страница 70: ...HYXE J01H 61 ...
Страница 71: ...HYXE J01H 62 ...
Страница 72: ...HYXE J01H 63 ...
Страница 73: ...HYXE J01H 64 ...
Страница 74: ...HYXE J01H 65 ...
Страница 75: ...HYXE J01H 66 ...
Страница 76: ...HYXE J01H 67 ...
Страница 115: ...HYDEͲE01H Hisense HYDE E01H 106 ...
Страница 116: ...HYDE E01H 107 ...
Страница 117: ...HYDE E01H 108 ...
Страница 119: ...HYXE A01H HYJE D02H HYXE A01H HYXE A01H HYXE A01H HYJE D02H HYJE D02H HYJE D02H HYDE E01H 110 ...
Страница 120: ...HYXE A01H HYJE D02H HYDE E01H 111 ...
Страница 121: ...HYDE E01H 112 ...
Страница 122: ...HYDE E01H 113 ...
Страница 123: ...HYDE E01H 114 ...
Страница 124: ...HYXE A01H HYJE D02H HYDE E01H 115 ...
Страница 125: ...HYXE A01H HYJE D02H HYDE E01H 116 ...
Страница 126: ...HYJE D02H HYDE E01H 117 ...
Страница 127: ...HYDE E01H 118 ...
Страница 128: ...HYJE D02H HYXE A01H HYDE E01H 119 ...
Страница 129: ...HYJE D02H HYJE D02H HYXE A01H Hisense Hisense HYDE E01H 120 ...
Страница 173: ...HYJ J01H 164 ...
Страница 174: ...HYJ J01H 165 ...
Страница 175: ...HYJ J01H 166 ...
Страница 176: ...HYJ J01H 167 ...
Страница 177: ...HYJ J01H 168 ...
Страница 178: ...HYJ J01H 169 ...
Страница 179: ... R QRW KDV WKLV IXQFWLRQ DV HW HYJ J01H 170 ...
Страница 180: ...HYJ J01H 171 ...
Страница 181: ...HYJ J01H 172 ...
Страница 182: ...HYJ J01H 173 ...