Demand Setting Procedure
Depress the "CHECK" switch for more than 3 seconds, and the central station is changed to the check mode.
*When there is any group in operation (with "RUN" indicator ON), the "CHECK" mode is not available.
Depress the "CHECK" switch and change the 7-segment indication for check to "5" (Demand Setting Mode).
The LCD indication of the central station is as shown below.
CHECK
ZONE
GROUP
The state of demand setting of the
indicated indoor unit is indicated.
"DEMAND" ON: Demand is set.
"DEMAND" OFF: Demand is not set.
The state of demand setting of each zone is indicated.
!
ON: There is one or more group with demand
setting in the zone.
!
OFF: There is no group with demand setting in the
zone.
The state of demand setting of each
group is indicated.
!
ON: Demand is set.
!
OFF: Demand is not set.
Address of Indoor Unit Set as Master
Unit of Group To Be Set
When the "CHECK" indication appears,
the central station is in the check mode.
Only the group with the master unit already set is
indicated. The group to be set is
fl
ickered.
Ref. No. of Indoor Unit Set as Master Unit of
Group To Be Set
"5" shows the demand
setting mode.
a. Select the demand function by depressing the
"LOUVER" switch.
b. Depress the "RUN/STOP" switch, and the
fl
ickering
indication of louver angle turns ON.
By depressing the "LOUVER"
switch, the indication of louver
angle is changed as shown in
right
fi
gure.
Demand1
Demand2
Demand3
The demand function can be set for all the indoor units, each zone or each group. The "
!
" indication of
"GROUP", for which the demand setting is already set, turns ON.
In the case where there is one or more group with demand setting in the zone, the "
!
" indication of "ZONE"
section turns ON.
#
Simultaneous Setting for All Indoor Units
a. Depress the "ZONE" switch to make all the zone No.
fl
icker. Then, the minimum refrigerant system address
and the minimum indoor unit address of the indoor
unit, which is set as the master unit, in all groups are
indicated.
#
Setting for Each Zone
a. Depress the "ZONE" switch and select the zone to set.
b. Depress the "GROUP" V
V
switch to make the group
No. to set
fl
icker. Then, the minimum Ref. No. and the
minimum I.U. Add. of the indoor unit set as the master
unit of all groups are indicated.
#
Setting for Each Group
a. Depress the "ZONE" switch and select the zone to set.
b. Depress the "GROUP" V
V
switch to select the group to
set. Then, the Ref. No. and I.U. Add. of the indoor unit
set as the master unit of selected group are indicated.
[Zone Selection]
Depress the "ZONE" switch, and the
fl
ickering
indication of zone No. is changed in order as shown
below.
* Only the zone No. to set is indicated.
* When selecting the all
fl
ickering state (Simultaneous
Operation for All Indoor Units), the groups to set are
automatically
fi
xed at the all
fl
ickering state. For
selecting the group, select the indication state except
all
fl
ickering.
[Group Selection]
Depress the "GROUP"
V
V
switch, and the
fl
ickering
indication of group No. is changed in order as shown
below.
*Only the group No. to set is indicated.
All
Flickering
1
2
16
Demand Function
Only the zone No. with
the group set as master
unit is indicated. The
zone No. to be set is
fl
ickered.
(1) Changing to Check Mode
(2) Changing to Demand Setting Mode
(3) Selection of Demand Function
(4) Selection of Group To Be Set
All
Flickering
1
2
4
3
HYJE-D02H
131
Содержание HYE-W01
Страница 7: ......
Страница 9: ......
Страница 16: ...Model HYXE J01H Wired Remote Control Switch 7 ...
Страница 22: ...Model HYDE E01H 7 Day Timer 13 ...
Страница 24: ...Model HCCS H128H2C1YM HCCS H128H2C1NM Central Control 15 ...
Страница 25: ...Model HCCS H247R4C1E Central Control 16 ...
Страница 26: ...Model HYJ J01H Central Control 17 ...
Страница 27: ...Central Control Model HYJM S01H 18 ...
Страница 34: ...HYXE G01H 25 ...
Страница 35: ...HYXE G01H 26 ...
Страница 46: ...HYXE J01H 37 ...
Страница 47: ...HYXE J01H 38 ...
Страница 48: ...HYXE J01H 39 ...
Страница 49: ...HYXE J01H 40 ...
Страница 50: ...HYXE J01H 41 ...
Страница 51: ...HYXE J01H 42 ...
Страница 52: ...HYXE J01H 43 ...
Страница 53: ...HYXE J01H 44 ...
Страница 54: ...HYXE J01H 45 ...
Страница 55: ...HYXE J01H 46 ...
Страница 56: ...HYXE J01H 47 ...
Страница 57: ...HYXE J01H 48 ...
Страница 58: ...HYXE J01H 49 ...
Страница 59: ...HYXE J01H 50 ...
Страница 60: ...HYXE J01H 51 ...
Страница 61: ...HYXE J01H 52 ...
Страница 62: ...HYXE J01H 53 ...
Страница 63: ...HYXE J01H 54 ...
Страница 64: ...HYXE J01H 55 ...
Страница 65: ...HYXE J01H 56 ...
Страница 66: ...HYXE J01H 57 ...
Страница 67: ...HYXE J01H 58 ...
Страница 68: ...HYXE J01H 59 ...
Страница 69: ...HYXE J01H 60 ...
Страница 70: ...HYXE J01H 61 ...
Страница 71: ...HYXE J01H 62 ...
Страница 72: ...HYXE J01H 63 ...
Страница 73: ...HYXE J01H 64 ...
Страница 74: ...HYXE J01H 65 ...
Страница 75: ...HYXE J01H 66 ...
Страница 76: ...HYXE J01H 67 ...
Страница 115: ...HYDEͲE01H Hisense HYDE E01H 106 ...
Страница 116: ...HYDE E01H 107 ...
Страница 117: ...HYDE E01H 108 ...
Страница 119: ...HYXE A01H HYJE D02H HYXE A01H HYXE A01H HYXE A01H HYJE D02H HYJE D02H HYJE D02H HYDE E01H 110 ...
Страница 120: ...HYXE A01H HYJE D02H HYDE E01H 111 ...
Страница 121: ...HYDE E01H 112 ...
Страница 122: ...HYDE E01H 113 ...
Страница 123: ...HYDE E01H 114 ...
Страница 124: ...HYXE A01H HYJE D02H HYDE E01H 115 ...
Страница 125: ...HYXE A01H HYJE D02H HYDE E01H 116 ...
Страница 126: ...HYJE D02H HYDE E01H 117 ...
Страница 127: ...HYDE E01H 118 ...
Страница 128: ...HYJE D02H HYXE A01H HYDE E01H 119 ...
Страница 129: ...HYJE D02H HYJE D02H HYXE A01H Hisense Hisense HYDE E01H 120 ...
Страница 173: ...HYJ J01H 164 ...
Страница 174: ...HYJ J01H 165 ...
Страница 175: ...HYJ J01H 166 ...
Страница 176: ...HYJ J01H 167 ...
Страница 177: ...HYJ J01H 168 ...
Страница 178: ...HYJ J01H 169 ...
Страница 179: ... R QRW KDV WKLV IXQFWLRQ DV HW HYJ J01H 170 ...
Страница 180: ...HYJ J01H 171 ...
Страница 181: ...HYJ J01H 172 ...
Страница 182: ...HYJ J01H 173 ...