51
Auto Reset Alarms
The following are codes for auto reset alarms with their meanings.
Codes Meaning
AL03
Low outlet water temperature (ST<AR01)
AL05
High outlet water temperature (ST>AR03)
AL17
Water flow switch
AL26 Antifreeze
AL35
Low suction pressure ,lower than 1.5bar
AL36
High discharge pressure ,higher than 42bar
AL37
Suction pressure transmitter alarm (B11)
AL38
Discharge pressure transmitter alarm(B12)
Display offline Wired remote control and main board communication trouble.
AL71
RT sensor trouble (over 150 ºC or lower than -35 ºC) (B1)
AL72
ST sensor trouble (over 150 ºC or lower than -35 ºC) (B2)
AL73
OT sensor trouble (over 150 ºC or lower than -35 ºC) (B3)
AL74
HT sensor trouble (over 150 ºC or lower than -35 ºC) (B4)
AL75
PT sensor trouble (over 150 ºC or lower than -35 ºC) (B5)
AL76
ET sensor trouble (over 150 ºC or lower than -35 ºC) (B6)
Manual Reset Alarms
The following are codes for manual reset alarms with their meanings.
Codes Meaning
AL20
Low suction temperature (AR08)
AL21
High exhaust gas temperature (over AR10 )
AL23 Phase
relay
AL24
Compressor overload
AL32
Low pressure alarms from transmitter times is over the limit(AR06)
AL33
High pressure alarms from transmitter times is over the limit(AR07)
Alarms
Содержание AS10S/L
Страница 3: ...2 Nomenclature ...
Страница 9: ...8 Positioning 1 550mm 600mm 550mm 600mm Positioning ...
Страница 35: ...34 Three curves of different ST05 setting User Guide ...
Страница 60: ...59 Dimensions AS10S L AS13S L 1096 550 500 1040 143 476 151 AS20S L Dimensions ...
Страница 63: ...62 AS20S L m3 h 10 20 30 1 0 2 0 3 0 4 0 40 KPa 5 0 Water Pressure Plots ...
Страница 64: ...63 Temperature and sensor resistance table Temperature and sensor resistance table ...
Страница 65: ...64 Temperature and sensor resistance table ...