23
Auxiliary Heating Electric Heater or Boiler (NO4)
There is a connection port (10-11) which can be used to activate and de-activate an
auxiliary electric heater or a boiler. The max current is 1 Amps therefore a contactor
must be applied to control auxiliary electric heater or boiler.
Hot Water Electric Heater (NO8)
There is a connection port (12-13) used to activate and de-activate hot water electric
heater . The max current is 1 Amps therefore a contactor must be applied to control
hot water electric heater. User parameter ST26 is the hours in interval to switch on hot
water heater to kill bacterial .After hot water temp. reaches ST27 pre-set water temp.,
hot water heater is switched off.
Electrical Connections
KM2
N
L1
PE
ELK
L2
L3