Cooling demand
In: B1
,
B2
On: B1
>
B1a+ST03
(
B1a is the measured sensor B1 temperature when the unit off condition is
met. The first time unit on condition B1a=ST01+5
)
Off: B2
<
ST01
Heating demand
In: B1,B2
On: B1
<
B1c-ST04
(
B1c is the measured sensor B1 temperature when the unit off condition is
met. The first time unit on condition B1c=ST02-5
)
Off: B2
>
ST02
Domestic hot water demand
In: B4 (HT)
On: B4<ST09-ST10
Off: B4>ST09