46
Para meter
Descriptions
Default
Min.
Max.
Unit
Res
CM01
Compressor minimum ON time
180
90
900
Sec.
1
CM02
Compressor minimum OFF time
300
90
1000
Sec.
1
CN01
EC fan Max. speed (cooling)
4
1
10
V
0.1
CN02
EC fan Max. speed (heating)
4
1
10
V
0.1
CN03
EC fan Min.. speed
3
1
10
V
0.1
CN04
EC fan Max speed (night mode)
4
1
10
V
0.1
CN05
EC fan PWM start ambient temp. (cooling)
35
0
50
℃
0.1
CN06
EC fan PWM end ambient temp. (cooling)
0
0
50
℃
0.1
CN07
EC fan PWM start ambient temp. (heating and DHW)
7
0
50
℃
0.1
CN08
EC fan PWM end ambient temp. (heating and DHW)
35
0
50
℃
0.1
EV05
PWM pump Max. speed
100
10
100
-
1
EV06
PWM pump Min. speed
30
10
100
-
1
EV07
Pump integral time
300
0
900
Sec.
1
EV08
Pump derivative time
1
0
90
Sec.
1
EV13
Pump control band on cooling
4
0.5
20
℃
0.1
EV14
Pump control band on heating
4
0.5
20
℃
0.1
SF06
Antifreeze start external temp.
2
0
10
℃
0.1
SF07
Antifreeze end external temp. difference
1
1
10
℃
0.1
SF08
Antifreeze start outlet water temp.
10
1
20
℃
0.1
SF09
Antifreeze end outlet water temp. difference.
5
1
10
℃
0.1
SF11
Discharge super heat setup
25
20
50
℃
0.1
SF12 Regulation
circle
12
1
90
S
0.1
SF20
Super heat setup
5
-72
99.9
℃
0.1
SF25 Refrigerant
type
R410A
AR01
Low outlet water temperature protection
5
1
10
℃
0.1
AR03
High outlet water temperature protection
58
1
100
℃
0.1
AR04
Water flow switch start-up delay time
30
1
300
Sec.
1
AR06
Low pressure alarm times within 24 hours
4
1
10
-
1
AR07
High pressure alarm times within 24 hours
6
1
10
-
1
AR08
low suction temperature protection
-2
-10
10
℃
0.1
AR09
Low pressure switch start-up delay time
300
10
1000
Sec.
1
AR10
High discharge gas temperature protection
115
100
130
℃
0.1
AR11
Antifreeze detect interval
30
1
1000
Min.
1
AR13
Low suction pressure alarm
1
0
25
bar
0.1
AR14
Low suction pressure alarm differential
1.5
0
15
bar
0.1
AR15
High discharge pressure alarm
42
0
50
bar
0.1
AR16
High discharge pressure alarm differential
6
0
15
bar
0.1
SF26
Crankcase heater start external temperature
10
0
30
℃
0.1
SF32
High pressure transmitter max. range
45
0
99
bar
0.1
SF34
EEV steps in defrost
250
0
470
stp
1
SF35
Compressor switch on delay on defrost
30
0
600
s
0.1
SF36
EEV steps limit
30
30
480
stp
1
SF37 EEV
delay
60
0
900
s
1
ST11
Minimum user setup cooling temperature
6
0
ST12
℃
0.1
ST12
Maximum user setup cooling temperature
40
ST11
60
℃
0.1
ST13
Minimum user setup heating temperature
20
0
ST24
℃
0.1
ST14
Maximum user setup heating temperature
55
ST13
80
℃
0.1
ST15
Minimum user setup hot water temperature
20
0
ST16
℃
0.1
ST16
Maximum user setup hot water temperature
55
ST15
80
℃
0.1
UI02 Manufacturer
password
0000
9999
-
1
Manufacturer parameter is code protected and only could be adjusted when unit is OFF.
CN02 Max. EC motor speed should not be over 4.6V in case of overheating.
Manufacturer parameters
Содержание AS10S/L
Страница 3: ...2 Nomenclature ...
Страница 9: ...8 Positioning 1 550mm 600mm 550mm 600mm Positioning ...
Страница 35: ...34 Three curves of different ST05 setting User Guide ...
Страница 60: ...59 Dimensions AS10S L AS13S L 1096 550 500 1040 143 476 151 AS20S L Dimensions ...
Страница 63: ...62 AS20S L m3 h 10 20 30 1 0 2 0 3 0 4 0 40 KPa 5 0 Water Pressure Plots ...
Страница 64: ...63 Temperature and sensor resistance table Temperature and sensor resistance table ...
Страница 65: ...64 Temperature and sensor resistance table ...