18
Electrical connection
Power Connection
Before connecting the power supply, please confirm the unit suits the power supply.
Breaker protection must be installed according to the max value stated in the
nameplate attached to the unit inside of the front panel.
The equipment must be installed via an isolator switch with a minimum breaking
gap of 3 mm
.
The power supply must conform to the specification on the unit’s nameplate. The
supply voltage must be within the range specified in the electrical data table. For
wiring connection, refer to the electric wiring diagram on the inside panel of the
unit.
When the building is equipped with a RCD the heat pump should be equipped
with a separate one
.
IMPORTANT:
During the installation of the unit, first make the water connections and then electrical
connections. If the unit is to be removed first disconnect the electrical connections, then the water
connections to reduce the chance of an electrical shock.
WARNING:
Disconnect the main power supply switch before servicing the system or handling any internal
parts of the unit.
In case of any major malfunction turn the unit off, disconnect the mains power supply and
contact a qualified service engineer.
Electrical Connections
Содержание AS10S/L
Страница 3: ...2 Nomenclature ...
Страница 9: ...8 Positioning 1 550mm 600mm 550mm 600mm Positioning ...
Страница 35: ...34 Three curves of different ST05 setting User Guide ...
Страница 60: ...59 Dimensions AS10S L AS13S L 1096 550 500 1040 143 476 151 AS20S L Dimensions ...
Страница 63: ...62 AS20S L m3 h 10 20 30 1 0 2 0 3 0 4 0 40 KPa 5 0 Water Pressure Plots ...
Страница 64: ...63 Temperature and sensor resistance table Temperature and sensor resistance table ...
Страница 65: ...64 Temperature and sensor resistance table ...