20 2392-01/02 MODULE BASE
Connect Hi to Hi and Lo to Lo of the module bases.
Only the CAN termination switch located on either side (a total of
two) should be turned on. After all connections have been com-
pleted, check to make sure that the resistance between Hi and Lo
is approx. 60
Ω
.
CAN Cable
Ground
• Ensure length of all cables do not exceed 100 m (328 feet).
• When electric potential occurs between the functional earth ter-
minals in the module base, CAN communications may not oper-
ate smoothly. When this happens, connect the shield wires of the
CAN cable to the respective module bases and only 1 earth wire
to earth, as shown in the diagram.
Содержание 2300 Smart Site
Страница 1: ...SMART SITE Instruction Manual 2300 February 2011 Revised edition 5 2300A981 05 11 02H...
Страница 13: ...Contents XII...
Страница 21: ...8 Service...
Страница 87: ...74 4 2304 20 PULSE MODULE...
Страница 105: ...92 5 2304 21 PULSE MODULE...
Страница 145: ...132 8 2321 20 WAVEFORM MODULE 8 1 4 Dimension Diagrams 103 9 1 Unit mm 96 1 110 1 103 3 1 94 6 1 68 5 1 4 1...
Страница 207: ...194 10 2332 20 POWER METER MODULE 10 1 4 Dimension Diagrams 94 5 1 103 3 1 103 9 1 110 1 96 1 45 5 1 4 0 5 Unit mm...
Страница 253: ...240 12 2342 20 OUTPUT MODULE...
Страница 275: ...262 14 2351 AIR MODULE 2352 20 WIRE MODULE...
Страница 285: ...272 15 2353 20 LAN MODULE...
Страница 317: ...304 18 2362 20 DC POWER MODULE...
Страница 345: ...332 20 2392 01 02 MODULE BASE...
Страница 347: ...334 21 Maintenance and Service...
Страница 348: ......
Страница 349: ......
Страница 350: ......
Страница 351: ......
Страница 352: ......
Страница 353: ......
Страница 354: ......
Страница 355: ......
Страница 356: ......
Страница 357: ......
Страница 358: ......
Страница 359: ......
Страница 360: ......
Страница 361: ......
Страница 362: ......
Страница 363: ......
Страница 364: ......
Страница 365: ......
Страница 366: ......