DNP V3.00
29
7.4.5 Internal Indications
Internal Indications
Object Number:
80
Request Function Codes supported:
1 (read), 2 (write)
Default Variation reported
when variation 0 requested:
1
Point
Index
Descriptions and Conditions
Writable?
0
IIN1-0
All Stations – set after a broadcast message (any message using a destination
address of 0xfff0 or above) has been received. Does not indicate an error condition.
No
1
IIN1-1
Class 1 event data available. Can be set at any time and does not indicate an error
condition.
No
2
IIN1-2
Class 2 event data available. Can be set at any time and does not indicate an error
condition.
No
3
IIN1-3
Class 3 event data available. Can be set at any time and does not indicate an error
condition.
No
4
IIN1-4
Time synchronization required. Can be set at any time and does not indicate an error
condition.
No
5
IIN1-5
Local mode. Set if some points are uncontrollable via DNP.
No
6 IIN1-6
Device
Trouble.
No
7
IIN1-7
Device restart. Set only under specific conditions. Does not indicate an error condition.
No
8
IIN2-0
Function Unknown. Generally means that the function code (octet 2 of the request
header) cannot be processed.
No
9
IIN2-1
Object Unknown. Generally means that the function code could be processed but the
object group / variation could not be processed.
No
10
IIN2-2
Parameter Error. Generally indicates that both the function code and object group /
variation could be processed but that the qualifier / range field is in error.
No
11
IIN2-3
Buffer Overflow. Indicates that an event buffer has overflowed, and that change
events, of at least one (1) type, have been lost.
No
12
IIN2-4
Already Executing
No
13 IIN2-5
Bad
configuration.
No
14
IIN2-6
Reserved. Always 0.
No
15
IIN2-7
Reserved. Always 0.
No