DNP V3.00

 

 

27 

7.4.3 Analog Inputs 

The following table lists Analog Inputs (Object 30). 

It is important to note that 16-bit and 32-bit variations of Analog Inputs, Analog Output Control Blocks, 
and Analog Output Statuses are transmitted through DNP as signed numbers.  Even for analog input points 
that are not valid as negative values, the maximum positive representation is 32767. 

For each point, the “Scaling and Units” column indicates the value of a transmitted 32767.  This also 
implies the value of a transmitted -32767.  The entry in the column 

does not

 imply a valid value for the 

point. 

Two (2) examples are provided:  In example 1, the point is un-scaled, represents kilowatts (a transmitted 
number 5 represents 5kW), and its valid range is from 0 to 10,000kW (meaning that the transmitted 
number will never exceed 10,000). 

In example 2, the point transmits A/D counts from a measurement of voltage.  The valid range is –2048 to 
2047 counts (the limits of the physical A/D converter), which represents -12V to +12V.  For this point, the 
representation of 32767 A/D counts, even though it is not a valid value for the point, is: 

 

(12/2047) * 32767 = 192V 

Always indicating the representation of 32767 in the tables below is a consistent method for representing 
scale, applicable to all scaling possibilities. 

The “Default Deadband” column is used to represent the absolute amount by which the point must change 
before an analog change event will be generated.  The “Default Change Event Assigned Class” column is 
used to represent the class (1, 2, 3, or none) in which detected change events will be reported.  Only the 
default values for these columns are documented here because the values may change in operation due to 
either local (user-interface) or remote (through DNP) configuration control. 

Analog Inputs 

Static (Steady-State) Object Number: 

30 

Change Event Object Number: 

32 

Reporting Deadband Object Number: 

34 

Request Function Codes supported: 

1 (read), 2 (write, deadbands only), 22 (assign class) 

Static Variation reported 
 

when variation 0 requested: 

2 (16-Bit Analog Input) 

Change Event Variation reported 
 

when variation 0 requested: 

2 (Analog Change Event Without Time) 

Reporting Deadband Variation reported 
 

when variation 0 requested: 

1 (16-Bit Reporting Deadband) 

Change Event Scan Rate: 

 

Point 

Index 

Name/Description 

Scaling and Units 

(representation of 32767) 

Reporting 

Deadband 

Initial Change Event 

Class (1, 2, 3 or none) 

Communication Firmware Rev.  

327.67 

DNP Rev.  

3.2767 

AT Firmware Rev.  

327.67 

Voltage Rating  

32767 Volts 

Current Rating  

32767 Amperes 

5 Voltage 

3276.7 

Volts 

10 

6 Current 

3276.7 

Volts 

20 

Equalize Time Remaining 

32767 Hrs 

Error 

Number 

32767 1 2 

Battery temperature 

32767 °C 

 

Содержание AT10.1 series

Страница 1: ...Operating Instructions AT10 1 AT30SERIES MICROPROCESSOR CONTROLLED FLOAT BATTERY CHARGER COMMUNICATIONS MODULE DNP3 Level 2 Modbus Protocols JA0102 04...

Страница 2: ...y standard modem and modem cable are also available Refer to the items listed below for part information and check off which items were supplied STANDARD COMMUNICATION MODULES Part No Communications M...

Страница 3: ...ort LEDs 17 6 RESET Button 18 7 DNP V3 00 19 7 1 Introduction 19 7 2 Device Profile 19 7 3 Implementation Table 22 7 4 Point List 25 7 4 1 Binary Inputs 25 7 4 2 Binary Output Status Points 26 7 4 3 A...

Страница 4: ...rminal Unit The advantage of ASCII allows less strict serial timing requirements without causing communication errors The advantage of RTU allows more data to be transmitted than ASCII mode for higher...

Страница 5: ...arrier Installation Steps Step 1 Turn off the ac and dc circuit breakers on the AT charger Using a voltmeter verify that all potential voltages on the I O panel are zero This includes the dc output te...

Страница 6: ...connect GROUND wire 244 to spade terminal next to connection plug J20 See assembly drawing JE5107 20 Step 7 Connect the serial communications connection a use TB11 for RS 232 see Section 3 2 1 b use T...

Страница 7: ...s The communications option supports RS 232 and RS 485 RS 232 is a standard serial communication used on personal computers It has a limited cable distance and is susceptible to electrical noise RS 48...

Страница 8: ...lines are disabled Disable the hardware handshaking lines by setting configuration switch S1 6 to the OFF position 8 TDX RDX COM CTS RTS 3 2 5 8 7 2 3 7 5 4 RS 232 PC Connection DB25 DB9 JUMPER NOT R...

Страница 9: ...operation the hardware handshaking lines are enabled Enable the hardware handshaking lines by setting configuration switch S1 6 to the ON position 8 TDX RDX COM CTS RTS 3 2 5 8 7 2 3 7 5 4 RS 232 PC C...

Страница 10: ...nation resistors requires a significantly lower value of biasing resistors which results in greater dc loading of the network Network design and biasing resistor calculations depend on the number of n...

Страница 11: ...ble the terminating resistor The device communicating with the charger needs its own terminating resistor installed 8 5 POSITIVE NEGATIVE COMMON SHIELD RS 485 Single Connection Figure 5 RS 485 Single...

Страница 12: ...of the network do not require the terminating resistor Move the jumper on J22 between pins 2 and 3 to disable the terminating resistor Figure 6 and Figure 7 show examples of multiple chargers on a RS...

Страница 13: ...rop 3 Chargers Charger No 2 Charger No 1 Charger No 3 7 5 8 5 Figure 7 RS 485 Multi Drop 3 Chargers Typical RS 485 applications tie the shield to earth ground at only one 1 location along the network...

Страница 14: ...of fiber connections compatible with standard B B and Dymec type converters Please refer to the following supplemental documentation for the available Fiber Optics Interface options EJ5230 04 http ww...

Страница 15: ...e This modem will not work with office digital phone systems The telephone line needs to be a dedicated analog phone line similar to most fax machines Plug in the ac power supply The host software nee...

Страница 16: ...1 Configuration Position Description ON position OFF position DIP S1 1 Setup Program Enabled Disabled DIP S1 2 Configuration Parameters User Values Factory Default Values DIP S1 3 Protocol DNP Modbus...

Страница 17: ...168 1 100 10 Netmask 255 255 255 0 11 Gateway 0 0 0 0 12 Enable Modbus over TCP IP 0 disabled 13 Modbus TCP Port 502 14 Enable DNP over TCP IP 0 disabled 15 DNP TCP Port 20000 16 RESTART Comm Board To...

Страница 18: ...NP TCP Port 20000 16 RESTART Comm Board To change a value or RESTART please select its item number After all parameters have been modified to the correct values turn off switch S1 1 Select RESTART Com...

Страница 19: ...s any time activity is detected on the network This activity may be messages to from other devices on the network In addition the flashing RXD LED only indicates that there are transitions on the netw...

Страница 20: ...of the RESET button The RESET switch when pushed will restart the AT Series Communication Module without resetting the charger s Main Control PC Board A1 This is useful when configuration changes are...

Страница 21: ...hould provide a complete interoperability configuration guide for the AT Series Communications Module interface The Implementation Table provided in Section 7 3 on page 22 The Point List Tables provid...

Страница 22: ...7 Fixed at 30000 ms if unsolicited messages is off Configurable if unsolicited messages is on See setup Unsolicited response notification delay 7 Fixed at 15000 ms Delay Measurement 100 ms Synchroniz...

Страница 23: ...LICITED Function codes supported Sends Static Data in Unsolicited Responses 7 Never When Device Restarts When Status Flags Change No other options are permitted Default Counter Object Variation 7 No C...

Страница 24: ...all 07 08 limited qty 17 28 index 129 response 00 01 start stop 17 28 index see note 2 1 2 Binary Input with Status 1 read 22 assign class 00 01 start stop 06 no range or all 07 08 limited qty 17 28 i...

Страница 25: ...l 07 08 limited qty 129 response 130 unsol resp 17 28 index 34 0 Analog Input Reporting Deadband Variation 0 is used to request default variation 1 read 00 01 start stop 06 no range or all 07 08 limit...

Страница 26: ...read 06 no range or all 07 08 limited qty 60 4 Class 3 Data 20 enbl unsol 21 dsbl unsol 22 assign class 06 no range or all No Object function code only see note 3 13 cold restart No Object function co...

Страница 27: ...Event Class 1 2 3 or none 0 HVDC Alarm 1 active 1 1 LVDC Alarm 1 active 1 2 DC Output Failure Alarm 1 active 1 3 AC input Failure Alarm 1 active 1 4 Positive Ground Fault Alarm 1 active 1 5 Negative...

Страница 28: ...operate 6 direct operate noack Point Index Name Description Methods 0 Equalize Mode Latch On Latch Off 0 float 1 equalize 1 Manual Timer Method Latch On 1 enabled 2 Manual Equalize Method Latch On 1 e...

Страница 29: ...ble to all scaling possibilities The Default Deadband column is used to represent the absolute amount by which the point must change before an analog change event will be generated The Default Change...

Страница 30: ...ction Codes supported 3 select 4 operate 5 direct operate 6 direct operate noack Point Index Name Description Scaling and Units representation of 32767 Valid Range 0 Float Voltage Setpoint 3276 7 Volt...

Страница 31: ...ed Can be set at any time and does not indicate an error condition No 5 IIN1 5 Local mode Set if some points are uncontrollable via DNP No 6 IIN1 6 Device Trouble No 7 IIN1 7 Device restart Set only u...

Страница 32: ...p n EJ5037 The Modbus protocol was implemented using the Modicon Modbus Protocol Reference Guide PI MBUS 300 Rev J 8 2 Supported Function Codes Below is the list of supported function codes 01 Read C...

Страница 33: ...on one 1 of the equalize methods the charger will turn off the other two 2 equalize methods automatically 8 3 2 Binary Inputs Address Name Description 10001 HVDC High Voltage DC Alarm 10002 LVDC Low V...

Страница 34: ...tery Temperature Temperature in Celsius 1 8 3 4 Holding Registers Address Name Description Multiplier 40001 Float Voltage Setpoint Float Voltage Setpoint 10 40002 Equalize Voltage Setpoint Equalize Vo...

Страница 35: ...1 0 48 0 76 0 30 0 50 0 130 110 0 141 0 117 0 149 0 120 0 175 0 80 0 126 0 9 2 Current Ranges Current Limit Current Rating Amperes Min Max 6 3 0 6 6 12 6 0 13 2 16 8 0 17 6 20 10 0 22 0 25 12 5 27 5 3...

Страница 36: ...from a remote location Meters Voltage Current Equalize Time Remaining Battery Temperature Setpoints Float Voltage Equalize Voltage Equalize Time Current Limit High DC Voltage Alarm Low DC Voltage Ala...

Страница 37: ...or higher already support the AT Series Communications Module option How do you connect to the AT Communications Module The AT Communication Module supports a serial connection using RS 232 RS 485 or...

Страница 38: ...will also need a modem The computer system will dial out to the AT Series charger The modem connected at the charger will answer the call and start communicating Refer to the special User Instruction...

Страница 39: ...Module Operating Manual JD5008 00 http www ATSeries net PDFs JD5008 00 pdf AT Communications Module Field Installation JD5012 00 http www ATSeries net PDFs JD5012 00 pdf AT Main Ctrl PC Board A1 Field...

Страница 40: ...the EN5004 0 Communications Module PC Board A12 may incur damage upon start up Charger Output 12 Vdc 24 Vdc 48 Vdc 130 Vdc Field Install Kit EJ5037 11 EJ5037 12 EJ5037 13 EJ5037 14 R29 Rating 11W 15 O...

Страница 41: ...ct the new Ground Wire 7 Route the remaining wires 194 195 which end at the 4 pin Molex type plug along the charger s main signal harness The wires will lead to the left side of the Main Control PC Bo...

Страница 42: ...awing itemized internal component layout electrical schematic with component ratings and a full connection diagram If the standard drawings featured in this manual are not sufficient please contact yo...

Страница 43: ...Series net PDFs JD5010 00 pdf AT Power Res R3 Field Installation JD5012 00 http www ATSeries net PDFs JD5012 00 pdf Main Ctrl PC Board A1 Field Installation DC5016 00 http www ATSeries net PDFs DC5016...

Страница 44: ...JA0102 04 TYPICAL APPLICATIONS FOR SCADA SYSTEMS http www atseries net PDFs JA0102 04 pdf JA0102 04 Rev 06 2021...

Отзывы: