DNP V3.00
25
7.4 Point
List
The tables in the following sections identify all the individual data points provided by this
implementation of DNP3.
7.4.1 Binary Inputs
Binary Input Points
Static (Steady-State) Object Number:
1
Change Event Object Number:
2
Request Function Codes supported:
1 (read)
22 (assign class)
Static Variation reported
when variation 0 requested:
1 (Binary Input Without Status)
Change Event Variation reported
when variation 0 requested:
2 (Binary Input Change with Time)
Change Event Scan Rate:
As indicated below, the scan rate for binary input
change events is 5000 ms)
Point
Index
Name/Description
Initial Change Event Class
(1, 2, 3 or none)
0
HVDC Alarm (1 = active)
1
1
LVDC Alarm (1 = active)
1
2
DC Output Failure Alarm (1= active)
1
3
AC input Failure Alarm (1 = active)
1
4
Positive Ground Fault Alarm (1 = active)
1
5
Negative Ground Fault Alarm (1 = active)
1
6
CAR (Summary) Alarm (1 = active)
1
7
HVDC Shutdown (1 = active)
1
8
LVAC Shutdown (1 = active)
1
9
Forced load sharing enabled (1 = enabled)
1
10
Temperate probe installed (1 = installed)
1
11
Defective temperate probe (1 = defective)
1
12
Equalize Mode - status of Binary Output: 0 (0 = float; 1 = equalize)
1
13
Manual Timer Method - status of Binary Output 1 (1 = enabled)
1
14
Manual Equalize Method - status of Binary Output 2 (1 = enabled)
1
15
Auto-Equalize Timer Method - status of Binary Output 3 (1 = enabled)
1
16
HVDC Shutdown Enabled - status of Binary Output 4 (1 = enabled)
1
17
Battery Type - status of Binary Output 5 (0= Lead; 1 = NiCD) 1