4 Start-up
HI 801 305 E Rev. 5.00
Page 43 of 72
4.4.4
Trip Function
The trip function evaluates the external and internal trip signals. The internal trip signals are
generated if the thresholds for the turbine rotation speed and acceleration are violated. The
external trip signals are signals that are read at the digital inputs (DI 02...DI 04) and generated
by external devices, e.g., machine monitoring systems. If the trip signal provides a trip condition,
a shut down is triggered (trip function) and the turbine is shut down. The digital outputs are de-
energized causing the quick stop of the turbine.
A shut down (trip function) can also be performed through the user program. To this end, the
parameters
Trigger Trip
and
Allow Trip Reset
are available in the SILworX programming tool.