3 Product Description
X-MIO 7/6 01
Page 28 of 72
HI 801 305 E Rev. 5.00
3.6.4
Terminal Assignment for Connector Boards with Screw Terminals
Designation
Signal
01a SCI01+
01b CI01+
01c DRI01+
01d CI01-
Designation
Signal
02a SCI02+
02b CI02+
02c DRI02+
02d CI02-
Designation
Signal
03a SCI03+
03b CI03+
03c DRI03+
03d CI03-
Designation
Signal
Designation
Signal
04a SDI01+
05a SDI02+
04b DI01+
05b DI02+
04c DI01-
05c DI02-
Designation
Signal
Designation
Signal
06a SDI03+
07a SDI04+
06b DI03+
07b DI04+
06c DI03-
07c DI04-
Designation
Signal
Designation
Signal
08a DO01+
09a DO02+
08b DO01-
09b DO02-
Designation
Signal
Designation
Signal
10a DO03+
11a DO04+
10b DO03-
11b DO04-
Designation
Signal
Designation
Signal
12a DO05+
13a C
12b DO05-
13b NO
13c
NC
Table 17: Terminal Assignment for Connector Boards with Screw Terminals
Cable plugs attached to the connector board pin headers are used to connect to the field zone.
The cable plugs feature the following properties:
Connection to the field zone
Cable plugs
13 pieces, with 2...4 poles
Wire cross-section
0.2…1.5 mm
2
(single-wire)
0.2…1.5 mm
2
(finely stranded)
0.2…1.5 mm
2
(with wire end ferrule)
Stripping length
6 mm
Screwdriver
Slotted 0.4 x 2.5 mm
Tightening torque
0.2…0.25 Nm
Table 18: Cable Plug Properties