3 Product Description
X-MIO 7/6 01
Page 20 of 72
HI 801 305 E Rev. 5.00
3.4.9
System Bus Indicators
The system bus LEDs are labeled
Sys
Bus.
LED
Color
Status
Description
On
Physical and logical connection to the system bus
module in slot 1.
Green
Blinking1
No physical connection to the system bus module in
slot 1.
A
Yellow Blinking1 The physical connection to the system bus module in
slot 1 has been established.
No connection to a (redundant) processor module
running in system operation.
On
Physical and logical connection to the system bus
module in slot 2.
Green
Blinking1
No physical connection to the system bus module in
slot 2.
B
Yellow Blinking1 The physical connection to the system bus module in
slot 2 has been established.
No connection to a (redundant) processor module
running in system operation.
A+B Off Off
Neither physical nor logical connection to the system
bus modules in slot 1 and slot 2.
Table 6:
System Bus Indicators
3.4.10
I/O Indicators
The LEDs of the I/O indicators are labeled
Channel
. LEDs CI 1 + CI 2, CI 3 + CI 4 and
CI 5 + CI 6 belong together. The LED with odd number outputs the frequency, while the LED
with even number outputs the rotation sense.
LED
Color
Status
Description
On
Frequency < 20 Hz at high level
Frequency > 20 Hz: No distinction between high and
low level is made for the LED.
Blinking2 Channel
fault
CI 1,
CI 3,
CI 5
Yellow
Off
Frequency < 20 Hz at low level
Channel not configured.
On
Rotation Sense, leading
CI 2,
CI 4,
CI 6
Yellow
Off
Rotation Sense, lagging
On
The related channel is active (energized).
Blinking2 Channel
fault
DI
1…4
Yellow
Off
The related channel is not active (de-energized).
On
The corresponding channel is active (energized)
Blinking2 Channel
fault
DO
1…5
Yellow
Off
The corresponding channel is not active (de-
energized)
On
The relay is energized
DO 6
Yellow
Off
The relay is de-energized
Blinking2
Field fault on at least one channel, e.g., open-circuit,
short-circuit, over-current, etc.
Field
Red
Off
No field fault displayed!
Table 7:
I/O Indicators
Содержание HIMax X-MIO 6 01