F3 DIO 8/8 01
3 Product Description
HI 800 179 E Rev. 2.00
Page 21 of 52
3.4.2
Communication
The remote I/O communicates with the associated controller via safe
ethernet
.
3.4.2.1
Connections for Ethernet Communication
Property
Description
Port
2 x RJ-45
Transfer standard
10BASE-T/100BASE-Tx, half and full duplex
Auto negotiation
Yes
Auto crossover
Yes
IP address
Freely configurable
1)
Subnet mask
Freely configurable
1)
Supported protocols
Safety-related:
safe
ethernet
Standard protocols: Programming and debugging tool
(PADT), SNTP
1)
The general rules for assigning IP address and subnet masks must be adhered to.
Table 9:
Ethernet Interfaces Properties
The two RJ-45 connectors with integrated LEDs are located on the bottom left-hand side of the
housing. Refer to Chapter 3.4.1.3 for a description of the LEDs' function.
The connection parameters are read based on the MAC address (media access control
address) defined during manufacturing.
The MAC address for the remote I/O is specified on a label located above the two RJ-45
connectors (1 and 2).
Figure 8: Sample MAC Address Label
The remote I/O is equipped with an integrated switch for Ethernet communication. For further
information on the integrated switch and safe
ethernet
, refer to Chapter
Communication
of the
system manual for compact systems (HI 800 141 E).
3.4.2.2
Network Ports Used for Ethernet Communication
UDP ports
Use
8000
Programming and operation with the programing tool
8001
Configuration of the remote I/O using the PES (ELOP II Factory)
8004
Configuration of the remote I/O using the PES (SILworX)
6010 safe
ethernet
123
SNTP (time synchronization between PES and remote I/O, PES and
external devices)
Table 10: Network Ports in Use