F3 DIO 8/8 01
4 Start-up
HI 800 179 E Rev. 2.00
Page 33 of 52
4.3.3
Digital Outputs of F3 DIO 8/8 01: DO 2 02
The following tables present the statuses and parameters for the output module (DO 2 02) in the
same order as given in the Hardware Editor.
4.3.3.1
Tab
Module
The
Module
tab contains the following system parameters:
System parameter
Data
type
R/W
Description
DO1.Error Code
WORD
R
Error codes for all digital outputs
Coding
Description
0x0001
Fault within the digital outputs
0x0002
Test of safety shutdown returns a fault
0x0004
Test of auxiliary voltage returns a fault
0x0008
FTT test of test pattern faulty
0x0010
Output switch test pattern faulty
0x0020
Output switch test pattern (shutdown test of the
outputs) faulty
0x0040
Active shutdown via WD faulty
0x0200
All outputs are switched off, total current
exceeded
0x0400
FTT test: 1st temperature threshold exceeded
0x0800
FTT test: 2nd temperature threshold exceeded
0x1000
FTT test: Monitoring of auxiliary voltage 1:
Undervoltage
DO2.Error Code
WORD
R
see
DO1.Error Code
Time on delay
UINT
W
Time on delay for 2-pole tests due to line capacities, inductive
and capacitive load, range 0…30 ms, 1 ms steps
Module Error Code
WORD
R
Module error code
Coding
Description
0x0000
I/O processing, if required with errors, see other
error codes
0x0001
No I/O processing (CPU not in RUN)
0x0002
No I/O processing during the booting test
0x0004
Manufacturer interface operating
0x0010
No I/O processing: invalid configuration
0x0020
No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not
plugged in
Module SRS
UDINT
R
Slot number (System Rack Slot)
Module Type
UINT
R
Type of module, target value: 0x00B4 [180
dec
]
Table 24: SILworX - System Parameters for Digital Outputs DO 2 02,
Module
Tab