4 Start-up
F3 DIO 8/8 01
Page 40 of 52
HI 800 179 E Rev. 2.00
System Signal
R/W
Description
Time on delay [UINT] W
Time on delay for 2-pole tests due to line capacities, inductive and
capacitive load, range 0…30 ms,
1 ms steps
Table 30: ELOP II Factory - Digital Output System Signals
4.4.5
Pulsed Outputs for F3 DIO 8/8 01
System signal
R/W
Description
Mod.SRS [UDINT]
R
Slot number (System Rack Slot)
Mod. Type [UINT]
R
Type of module, target value: 0x005B [91
dec
]
Mod. Error Code
[WORD]
R Module
error
code
Coding
Description
0x0000
I/O processing, if required with errors, see other error
codes
0x0001
No I/O processing (CPU not in RUN)
0x0002
No I/O processing during the booting test
0x0004
Manufacturer interface operating
0x0010
No I/O processing: invalid configuration
0x0020
No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not plugged in
DO.Error Code
[WORD]
R
Error code of the TO unit as a whole
Coding
Description
0x0001
Error of the TO unit as a whole:
DO
xx
.Error Code
[BYTE]
R
Error code of the individual digital pulsed output channels:
Coding
Description
0x01
Fault in the digital output module
DO[xx].Value [BOOL] W
Output value for TO channels:
1 = output energized
0 = output de-energized
Pulsed outputs must not be used as safety-related outputs!
Table 31: ELOP II Factory - System Signals for the Pulsed Outputs