F3 DIO 8/8 01
3 Product Description
HI 800 179 E Rev. 2.00
Page 19 of 52
3.4.1
LED Indicators
The light-emitting diodes (LEDs) indicate the operating state of the remote I/O. The LEDs are
classified as follows:
Operating voltage LED
System
LEDs
Communication
LEDs
I/O
LEDs
3.4.1.1
Operating Voltage LED
LED
Color
Status
Description
On
24 VDC operating voltage present
24 VDC
Green
Off
No operating voltage
Table 5:
Operating Voltage LED
3.4.1.2
System LEDs
While the system is being booted, all LEDs are lit simultaneously.
LED
Color
Status
Description
On
Device in RUN, normal operation
Blinking
Device in STOP
A new operating system is being loaded.
RUN
Green
Off
The device is not in the RUN state.
On
The device is in the ERROR STOP state.
Internal fault detected by self-tests, e.g., hardware faults or cycle time
overrun.
The processor system can only be restarted with a command from the
PADT (reboot).
Blinking
If ERROR blinks and all others LEDs are lit simultaneously, the boot
loader has detected an operating system fault in the flash memory and
waits for a new operating system to be loaded.
ERROR
Red
Off
No faults detected.
On
A new configuration is being loaded into the device.
Blinking
The device switches from INIT to STOP
A new operating system is being loaded into the flash ROM.
PROG
Yellow
Off
No configuration or operating system is being loaded.
FORCE
Yellow Off
The FORCE LED of a remote I/O is not functioning. The FORCE LED of
the associated controller serves to signal the forcing of a remote I/O.
On
The loaded configuration is not valid.
The new operating system is corrupted (after OS download).
Blinking
Fault while loading a new operating system
One or multiple I/O faults occurred.
FAULT
Yellow
Off
None of the described faults occurred.
Blinking
Operating system emergency loader active.
OSL
Yellow
Off
Operating system emergency loader inactive.
Blinking
OS and OSL binary defective or hardware fault, INIT_FAIL.
BL
Yellow
Off
None of the described faults occurred.
Table 6:
System LEDs