4 Start-Up
F20
Page 38 of 56
HI 800 143 E Rev. 1.01
4.3.2.3
DIO 8/8: DI Channels
Tab
The
DIO 8/8: DI Channels
tab contains the following system parameters:
System parameter
Data
type
R/W Description
Channel no.
---
R
Channel number, defined by default
-> Error Code
[BYTE]
BYTE
R
Error codes for the digital input channels
Coding
Description
0x01
Fault in the digital input module
0x10
Short-circuit of the channel
0x80
Intermittence between pulsed output TO
and digital input DI, e.g.,
Open-circuit
Open
switch
L+ low voltage
-> Value [BOOL]
BOOL
R
Input values for the digital input channels
0 = input de-energized
1 = input energized
Pulse Channel
[USINT] ->
USINT
W
Source channel for pulsed supply
Coding
Description
0 Input
channel
1
Pulse of the 1st TO channel
2
Pulse of the 2nd TO channel
… …
4
Pulse of the 4th TO channel
Table 29: SILworX - System Parameters for the Digital Inputs,
DIO 8/8: DI Channels
Tab