3 Product Description
F20
Page 30 of 56
HI 800 143 E Rev. 1.01
Digital inputs
Number of inputs
8 (non-galvanically isolated)
High level: Voltage
Current
input
15...30 VDC
≥
2 mA at 15 V
Low level:
Voltage
Current
input
max. 5 VDC
max. 1.5 mA (1 mA at 5 V)
Switching point
typ. 7.5 V
Sensor supply LS+
2 x 20 V / 100 mA (at 24 V), short-circuit-proof
Digital outputs
Number of outputs
8 (non-galvanically isolated)
Output
≥
L+ minus 2 V
Output current
Channels 1...3 and 5...7: 0.5 A at 60 °C
Channels 4 and 8: 1 A at 60 °C, 2 A at 50 °C)
Minimum load
2 mA for each channel
Internal voltage drop
max. 2 V at 2 A
Leakage current (with low
level)
max. 1 mA at 2 V
Behavior with overload
The affected output is switched off and re-started
cyclically.
Total output current
max. 7 mA
Upon overload, all outputs are switched off and cyclically
switched on again
Table 21: Specifications for the Digital Inputs and Outputs
Pulsed outputs
Number of outputs
4 (non-galvanically isolated)
Output
approx. 20 V (depending on the operating voltage)
Output current
approx. 60 mA
Minimum load
none
Behavior with overload
4 x
≥
19.2 V, short-circuit current 60 mA at 24 V
Table 22: Specifications for the Pulsed Outputs